3.5 Coils and

Related Cooling

Components

The DX cooling system is equipped with copper finned

coils.

Inspect all cooling

system coils at the beginning of the cooling season or more often if needed. Follow

the cleaning instructions below. If additional cleaning is required or if a coil must be

removed for any reason, consult the factory. Be prepared to provide rating plate and

specific installation information.
Condensing Coil Access - The condensing coils are visible on the side of the unit

(below the condenser fans).

Condenser Coil

Cleaning Instructions

1. Verify that the electrical power has been turned off and the disconnect switch

locked.

2. Use a soft brush to remove any dirt and debris from the coils.
3. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based

coil cleaner is recommended). Due to possible damage to the coil,

DO NOT use

high pressure spray.

4. When clean, rinse with cool, clean water.

Evaporator Coil Access - The evaporative coils can be accessed by opening the coil

cabinet door.

Inspect coils for debris, dirt, grease, lint, pollen, mold, or any element which would

obstruct heat transfer or airflow. Inspect coils and tubing for physical damage. Inspect

feeders, piping connections, coil headers, and return bends for signs of fatigue, rub-

bing, and physical damage.
Clean the coils annually, or more often if needed. Use the proper tools and follow the

instructions carefully to avoid damaging the coil. Use of a non-acid based coil cleaner

is recommended. Due to possible damage to the coil,

DO NOT use high pressure

spray.

Evaporator

Coil Cleaning

Instructions:

1. Verify that the electrical power has been turned off and the disconnect switch

locked.

2. Open the cooling coil door.
3. Use a soft brush to remove any dirt and debris from both sides of the coil.
4. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based

coil cleaner is recommended). Due to possible damage to the coil,

DO NOT use

high pressure spray. First spray the leaving airflow side, then the inlet airflow side.
As much as possible, spray the solution perpendicular to the face of the coil.
Follow the instructions on the cleaning solution. When cleaning process is

complete, rinse both sides with cool, clean water.

3.4 Condenser Fans

Depending on the model size, there are two or four condenser fans. Fan motors may

be either standard efficiency or ECM speed control. If parts need to be replaced, use

only factory authorized replacement parts.