beautypg.com

Length = 6 ft - (.75 x lift) – Reznor OH Unit Installation Manual User Manual

Page 7

background image

Form I-OH, PN 120390 R5, Page 7

part of a burner, connect a pressure relief valve into the discharge line between the

pump and the shutoff valve and arrange to return surplus oil to the supply tank or to

bypass it around the pump, unless the pump includes an internal bypass.
Any fuel oil line incorporating a heater shall be provided with a relief valve arranged

to discharge to the return line when any valve, pump, or other device may prevent the

release of excessive pressure because of the expansion of the oil when heated.
Where oil is supplied to a burner requiring uniform flow by gravity feed and a constant

level valve is not incorporated in the burner assembly or the oil is not supplied by an

automatic pump, install a constant level valve in the supply line at the gravity tank or as

close as practical, to ensure uniform delivery of oil to the burner. The vent opening of

the constant level valve should be connected by piping or tubing to the outside of the

building, unless the constant level valve is provided with an anti-flooding device. Do

not connect the vent piping or tubing of constant level valves to tanks or tank vents.
Prior to entering enclosures, such as vaults or pits, where pumps and accessories are

installed, provide for adequate ventilation.

6.1.1 Standard Single Stage Burner Pump with Single Supply Pipe

The standard burner is equipped with a single-stage, 3450 RPM pump with the lift

capacity shown in

FIGURE 4. Maximum lift is 8 ft (2.4M). Fittings, valves and filters

will reduce total line length allowed. Check component manufacturer's information for

equivalent length reduction required to compensate for pressure loss. A one-pipe sup-

ply system must be absolutely airtight, or leaks and/or loss of prime may result. Follow

instructions in Paragraph 8.2, Check-Test-Start (Operating Procedure) to bleed the

line. Bleed for 15 seconds after last air is seen from easy flow bleed valve to be certain

lines are air free.

Fuel Unit

Auxiliary Filter

Maximum

One Pipe

Lift

8 ft (2.4M)

Inlet

Shutoff Valve

Oil

Tank

1-1/4” (32mm) minimum

Fill

Pipe

Air

Vent

FIGURE 4 - Single Pipe Supply System (single-stage burner pump)

Maximum Horizontal Line Length (ft) by

Heater Size and Size of Tubing

Maximum Horizontal Line Length (M) by

Heater Size and Size of Tubing

Lift

95

140

190

Lift

95

140

190

(ft)

3/8" 1/2" 3/8" 1/2" 3/8" 1/2"

(M)

3/8" 1/2"

3/8" 1/2" 3/8" 1/2"

0

822 3158 556 2222 423 1667

0.0

251

963

169

677

129 508

1

719 2763 486 1944 370 1458

0.3

219

842

148

593

113

444

2

616 2368 417 1667 317 1250

0.6

188

722

127

508

97

381

3

514 1974 347 1389 264 1042

0.9

157

902

106

423

80

318

4

411 1579 278 1111 211 833

1.2

125

481

85

339

64

254

5

308 1184 208 833 158 625

1.5

94

361

63

254

48

191

6

205

789 139 556 106 417

1.8

62

240

42

169

32

127

7

103

395

69

278

53

208

2.1

31

120

21

85

16

63

8

0

0

0

0

0

0

2.4

0

0

0

0

0

0

Length =

6 ft - (.75 X Lift)

(.0086 for 3/8" tubing or

.00218 for 1/2" tubing)

X

(Firing Rate in GPH - OH95, .085;

OH140, 1.25; OH190, 1.35)

Formula for determining figures (ft) in

TABLE 5 above.

TABLE 5 - Maximum Horizontal Line Length

(ft/M) with a Single Pipe Supply System

6.1.2 Two-Pipe Supply System with Standard Single-Stage Pump

or Optional Two-Stage Pump

A two-pipe supply system may be used with the standard burner pump or with a two-

stage pump if Option BZ1 was ordered. The two-stage pump provides dual pumping

gears. To install the two-pipe supply system, remove the 1/4" plug from the return line

port and insert the 1/16" bypass plug (Shipped with the burner pump; see

FIGURE

17, page 17.). Attach the inlet and return lines. Always terminate the return line 3 to 4

inches (76 to 102mm) above the supply line inlet. See

FIGURE 5.