beautypg.com

Mechanical (cont'd), 2 venting and combustion air (cont'd) – Reznor OH Unit Installation Manual User Manual

Page 12

background image

Form I-OH, PN 120390 R5, Page 12

140 and 190 use 8" diameter pipe; for Size 95, use 7" diameter pipe. Keep the length of

the vent pipe connection as short and direct as possible. As it leaves the heater, slope

the horizontal run upward at least one inch for each three feet of pipe. The horizontal

run should not be longer than one-half of the vertical or chimney height and never over

ten feet (3M) unless a draft inducer is being installed.
If the vent pipe connector passes through a combustible wall, it must be guarded at

the point of passage by either a metal ventilated thimble not less than 12" (305mm)

larger in diameter than the pipe, or a metal or burned fireclay thimble built in brickwork

or other approved fireproofing material extending not less than 8" (203mm) beyond all

sides of the thimble. If a thimble is not installed, all combustible material in the wall or

partition must be cut away 9" (229mm) from the pipe. If any material is used to close

this opening, it must be non-combustible.
Fasten all vent piping with sheetmetal screws and support horizontal vent pipe from

above with noncombustible straps. Avoid sharp turns in the vent pipe or other construc-

tion features that would create resistance to the flow of the flue gases. Do not use a

manually operated damper or any other device that will obstruct the free flow of the

flue gases.
The end of the vent pipe connection must not extend past the inside wall of the chim-

ney. A thimble may be used in the chimney connection to facilitate removal for cleaning.

The thimble should be permanently cemented in place with high-temperature cement.

Draft Regulator

Requirements

6. Mechanical

(cont'd)

6.2 Venting and

Combustion Air

(cont'd)

Loosen knob and

slide in slot to

change draft.

INCREASE

DECREASE

Option DB1,

Barometric

Draft

Regulator

FIGURE 11 - Draft

Regulator, Option

DB1 (Required in

Canada. Option

DB1 or equivalent

is required in U.S.)

6.2.1 Venting (cont'd)

Canadian Installation - Option DB1 certified barometric draft regulator is required and

must be installed near the heater flue outlet. The preferred mounting location for the

draft regulator is in the vertical flue pipe (See

FIGURE 11). Depending on the venting

arrangement, the alternate location for installing the draft regulator is in the horizontal

run. Follow the manufacturer's instructions included with the draft regulator.
U.S.A. Installation - A UL listed type barometric draft regulator such as Option DB1,

must be installed (See Installation Note below for exception) in the flue near the heater

flue outlet. The preferred mounting location for the draft regulator is in the vertical flue

pipe (See FIGURE 5). Depending on the venting arrangement, the alternate location

for installing the draft regulator is in the horizontal run. Install the draft regulator accord-

ing to the manufacturer's instructions.
(INSTALLATION NOTE: Do not install a barometric draft regulator if the installation

includes an optional outside combustion air inlet, Option DE1.)

Optional Draft Inducer Relay (Option DH1)

A field-supplied U.L. (U.S.A.) or CSA/ULC (Canada) listed draft inducer is required

when the draft in the flue measures less than .04" w.c. on a draft gauge. Instructions

for measuring draft are included in Paragraph 8.2. A relay (Option DH1) is available for

connecting the draft inducer.
When a draft inducer is installed, a safety provision must be made to shut off the fuel

supply to the burner in the event of the failure of the draft inducer. See optional exhaust

flow safety switch on the wiring diagram.