beautypg.com

Electrical supply and connections, 1 general, 2 supply and line wiring – Reznor OH Unit Installation Manual User Manual

Page 13

background image

Form I-OH, PN 120390 R5, Page 13

6.2.2 Combustion Air

WARNING: Exercise care to ensure that an adequate supply of

combustion air is available and free to enter the air openings

on all units.

Openings equal to one inch square per each 1,000 BTUH

should be used to allow combustion air to enter the room

where the heater is installed.

R.W. Beckett

Model AF Burner

Adhesive-

backed

Gasket

Air

Damper

Adjust-

ment

Air Damper

Pump

Mounting

Screws

Fuel Unit

Outside

Combustion

Air Intake

Assembly

Extra-long

Coupling

FIGURE 12 - Optional

Outside Combustion

Air Intake Adapter,

Option DE1

Optional Outside Combustion Air Intake Adapter Kit, UL Listed,

Option DE1 (shipped separately) (Not available for Canadian

installation.)

The combustion air adapter will provide outside air for combustion. Follow the manu-

facturer's instructions furnished with the kit.

7. Electrical

Supply and

Connections

7.1 General

All wiring must be done in accordance with the National Electric Code or CSA Standard

C22.1, Canadian Electrical Code, Part 1, and local ordinances. In many localities, No.

14 wire run in rigid conduit must be used, but where permissible, two and three wire BX

is recommended, particularly for connections to the controls and burner motor. A cutoff

switch for the main 115 volt line to the burner should be mounted on a fireproof wall in

an accessible place close to the burner.
The heater is equipped with low voltage controls (24V) for thermostat control. See

separate instructions for any optional equipment provided.

7.2 Supply and Line

Wiring

TABLE 8 - Electrical

Ratings, 115V, 60 Hz

Check the rating plate on the heater for supply voltage and current requirements. A

separate line voltage supply with fused disconnect switch should be run directly from

the main panel to the heater, making connection to leads in the junction box. All exter-

nal wiring must be within approved conduit. See wiring diagram in the heater junction

box. Conduit from the disconnect switch must be run so as to not interfere with heater

service access.
All replacement wiring must be type SF, SEWF, TW, TEW or equivalent. Use 18 gauge

wire for control circuits; 14 gauge or larger, depending on current requirements, for line

connections.

OH

Size

Total Current

Amperes

Minimum Circuit

Ampacity

Minimum

Fuse Size

95

6

8

15

140

7

9

15

190

7

9

15