Form I-OH, PN 120390 R5, Page 11

WARNING: Failure to provide proper venting could result in

death, serious injury, and/or property damage. Unit must be

connected to flue having sufficient draft to ensure safe and

proper operation. Unit must be properly vented to the outside

of the building. Safe operation of any gravity-vented heating

equipment requires a properly operating vent system, correct

provision for combustion air, and regular maintenance and

inspection. See Hazard Levels, page 2.

6.2 Venting and

Combustion Air

6.1.6 Optional Solenoid Valve

(Option DD1, shipped separately)

Use of the optional solenoid valve is recommended with the pressurized oil delivery

system (Paragraph 6.1.4). It is designed to operate simultaneously with the burner

motor.

6.1.7 Optional Oil Safety Valve (OSV)

(Option DC1, shipped

separately)

The oil safety valve is opened by the slight vacuum created by the burner pump and

closes when the vacuum condition subsides. This prevents siphoning of the supply

line and eliminates spill, if any leaks develop downstream from the OSV.

Use of the

optional oil safety valve is highly recommended.

6.1.8 Check Valve

The check valve prevents reverse flow of oil maintaining static head pressure between

the check valve and the automatic valve on the burner, thus preventing siphoning.

Check valves are field provided and are not needed when an oil safety valve (Option

DC1) is used.

6.2.1 Venting

Masonry chimneys and metal chimneys must be built in accordance with accepted

building code practice. A Class A chimney or equivalent is required for this heater.

Standards for chimneys can be found in NFPA Standard No. 211, published in National

Fire Codes, Volume 4; the National Building Code of the American Insurance Associa-

tion, New York, NY; ULC Standards for chimneys; or the National Building Code of

Canada published by the National Research Council, Ottawa.
If an existing masonry or metal chimney is being used, prior to installing the heater,

clean and inspect the chimney. Make any necessary repairs and be sure that the chim-

ney meets all requirements.
If an approved factory-built chimney is being installed, be sure that it meets all require-

ments and install it according to the manufacturer's instructions. If a field-constructed

metal chimney is being installed, follow all of the requirements listed below.
• Use at least 8" (203mm) diameter vent pipe for Sizes 140/190 and at least 7"

(178mm) diameter for Size 95.

• Use either 24-gauge or heavier, galvanized steel or triple-wall stainless steel vent

pipe. (Triple-wall stainless steel vent pipe is recommended.)

• If the venting arrangement includes passing through a ceiling, triple-wall stainless

vent pipe is required above the ceiling. The point of passage through a ceiling

must be guarded by a metal ventilated thimble not less than 12" (305mm) larger in

diameter than the pipe.

• Install a tee with a cleanout cap at the bottom of the vertical rise.
The smallest dimension of the chimney must be at least 8" in diameter for Size 140

and 190 heaters and at least 7" in diameter for a Size 95 model. The chimney must

be at least three feet (.9M) above the highest point of exit where it passes through the

roof, and at least two feet (.6M) higher than any portion of a building within ten feet

(3M) of the chimney. Total chimney height must be a minimum of eight feet (2.4M). The

chimney must be capable of maintaining a steady draft of .04" w.c. If draft is below the

minimum required, a draft inducer must be installed.
For the vent connection from the flue outlet of the heater to the chimney, use vent pipe

of either 24-gauge or heavier galvanized steel or triple-wall stainless steel. For Sizes