Terminal descriptions – Interlogix NX-6V2 Rev C Installation Manual User Manual
Page 9

Chapter 1: Reporting codes
NX-6V2 Control Panel Installation Manual
5
Terminal descriptions
Table 2 below describes the terminals shown in the wiring diagram.
Table 2: NX-6V2 terminals
Terminal
Description
R1
House telephone ring (gray wire on the standard RJ-31X card).
R
Telephone ring (red wire on the standard RJ-31X cord).
T
Telephone tip (green wire on the standard RJ-31X cord).
T1
House telephone tip (brown wire on the standard RJ-31X cord).
EARTH
Earth ground. Connect to a cold water pipe or a 6 to 10 ft. driven rod.
AC
AC input. Connect to a 16.5 V 40 or 50 VA Class II UL approved transformer.
BELL+ and
BELL-
If used as a siren output (default), the speaker rating is 15 watt at 8 or 16
ohms, or 30/40 watt at 4, 8, or 16 ohms. If voltage output is selected in
Location 37, this output becomes voltage output, 12 VDC, 1 A maximum load.
A 3.3 kohm resistor is required across the bell terminals when a 12 VDC siren
is used. If no resistor is used, you may experience voltage leakage into the
siren, which causes these devices to output a s mall signal.
DATA
Connect to the data terminal on the keypads and the expanders. Maximum
number of devices: 16 keypads plus three other devices .
COM
Connect to the common terminal on the keypads and the expanders.
POS
Connect to the POS terminal on the keypads and the expanders. Individually,
this terminal is limited to 1 amp. Combined, this terminal and AUX PWR+ are
limited to 2 amps total current.
COM
Connect negative wire of powered devices such as motion detectors and
smoke detectors.
AUX+
Connect positive wire of all powered devices except smoke detectors and
keypads. Individually, this terminal is limited to 1 amp. Combined, this terminal
and KP POS are limited to 2 amps total current.
ZONE 6
Connect to one side of the zone 6 loop. Connect the other side to the COM
terminal. Open or short causes an alarm.
COM
Common (-) terminal for zones 5 and 6.
ZONE 5
Connect to one side of zone 5 loop. Connect the other side to the COM
terminal. Open or short causes an alarm.
ZONES 1 to 4
Connect as describes for zones 5 and 6.
AUXOUT 4
(SMOKE +)
Smoke detector power 12 VDC (for those jurisdictions that allow the Priority
zone to be used with smoke detectors). Current limited to 50 mA when output
is positive and 250
A when output is negative. This output defaults to Smoke
Power, but can be reconfigured.
AUXOUT 1 to 3
Connect negative lead of low current device. For example, relays or LEDs
(install 1 kohm resistor in series if connected to an LED). Connect positive
lead of device to AUX+. Current is limited to 50 mA.