Chapter 2: Reporting codes
NX-6V2 Control Panel Installation Manual
31
Location 25 - Zones 1 to 8 zone type
Location 25 has eight segments of numerical data. Use this location to program
the zone type for zones 1 to 8. Use segment 1 for zone 1, segment 2 for zone 2,
etc. The segment defaults are 3, 5, 6, 6, 6, 6, 6, 6.
Location 26 - Zones 1 to 8 partition
Location 26 has eight segments of feature selection data. Use this location to
select the partitions (1 or 2) that zones 1 to 8 reside in. Each segment
corresponds to a zone (segment 1 to zone 1, segment 2 to zone 2, etc.). In each
segment, enter 1 for partition 1 or 2 for partition 2.
Location 27 - Zones 9 to 16 zone types
Location 27 has eight segments of numerical data. Use this location to program
the zone type for zones 9 to 16. Use segment 1 for zone 9, segment 2 for zone
10, etc. The segment defaults are 6, 6, 6, 6, 6, 6, 6, 6.
Location 28 - Zones 9 to 16 partition
Location 28 has eight segments of feature selection data. Use this location to
select the partitions (1 or 2) that zones 1 to 8 reside in. Each segment
corresponds to a zone (segment 1 to zone 1, segment 2 to zone 2, etc.). In each
segment, enter 1 for partition 1 or 2 for partition 8.
Locations 29 to 36 - Reserved