2 alarms table – EVCO c-pro nano NAV User Manual
Page 32

C-PRO NANO AND MICRO NAV APPLICATION MANUAL
Page 32
7.2
Alarms Table
 
Below is a list of all alarms managed by the application. The order of presentation is the same as the 
order with which the alarms are displayed when active. The alarms code as the number of the unit 
where the alarm is occurring as the last number (in the table indicated by n) 
 
Code 
Alarm description
Typ
e
Consequence
Notes
COMn
Communication error with the unit n
Auto
Compressor OFF 
Salt water pump 
OFF 
Fresh water pump 
OFF* 
Delayed 
Always active 
ES1n
Fresh water input temp. probe broken 
or disconnected error 
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
Always active 
ES2n
Fresh water output temp. probe broken 
or disconnected error 
Man
u
Compressor OFF 
Salt water pump 
OFF 
Fresh water pump 
OFF* 
Instant 
Always active 
ES3n
Condenser gas input temp. probe 
broken or disconnected error 
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
Always active 
ES4n
Evaporator gas output temp. probe 
broken or disconnected error 
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
Always active 
AHPn
High pressure alarm
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
Always active 
ALPn
Low pressure alarm
Auto
/Ma
nu
Compressor OFF 
Salt water pump 
OFF 
Compressor start-
up delay. 
Always active 
AFLn
Flow switch alarm
Man
u
Compressor OFF 
Salt water pump 
OFF 
Fresh water pump 
OFF* 
Delayed at start-
up 
Only with pump 
on 
AT1n
Condenser high temperature alarm
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
In summer only 
AT2n
Evaporator low temperature alarm
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
In summer only 
AT3n
Condenser low temperature alarm
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
In winter only 
AT4n
Evaporator high temperature alarm
Man
u
Compressor OFF 
Salt water pump 
OFF 
Instant 
In winter only 