C-PRO NANO AND MICRO NAV APPLICATION MANUAL

Page 32

7.2

Alarms Table


Below is a list of all alarms managed by the application. The order of presentation is the same as the
order with which the alarms are displayed when active. The alarms code as the number of the unit
where the alarm is occurring as the last number (in the table indicated by n)

Code

Alarm description

Typ

e

Consequence

Notes

COMn

Communication error with the unit n

Auto

Compressor OFF
Salt water pump
OFF
Fresh water pump
OFF*

Delayed
Always active

ES1n

Fresh water input temp. probe broken
or disconnected error

Man

u

Compressor OFF
Salt water pump
OFF

Instant
Always active

ES2n

Fresh water output temp. probe broken
or disconnected error

Man

u

Compressor OFF
Salt water pump
OFF
Fresh water pump
OFF*

Instant
Always active

ES3n

Condenser gas input temp. probe
broken or disconnected error

Man

u

Compressor OFF
Salt water pump
OFF

Instant
Always active

ES4n

Evaporator gas output temp. probe
broken or disconnected error

Man

u

Compressor OFF
Salt water pump
OFF

Instant
Always active

AHPn

High pressure alarm

Man

u

Compressor OFF
Salt water pump
OFF

Instant
Always active

ALPn

Low pressure alarm

Auto

/Ma

nu

Compressor OFF
Salt water pump
OFF

Compressor start-
up delay.
Always active

AFLn

Flow switch alarm

Man

u

Compressor OFF
Salt water pump
OFF
Fresh water pump
OFF*

Delayed at start-
up
Only with pump
on

AT1n

Condenser high temperature alarm

Man

u

Compressor OFF
Salt water pump
OFF

Instant
In summer only

AT2n

Evaporator low temperature alarm

Man

u

Compressor OFF
Salt water pump
OFF

Instant
In summer only

AT3n

Condenser low temperature alarm

Man

u

Compressor OFF
Salt water pump
OFF

Instant
In winter only

AT4n

Evaporator high temperature alarm

Man

u

Compressor OFF
Salt water pump
OFF

Instant
In winter only