EVCO c-pro nano NAV User Manual
Page 18

C-PRO NANO AND MICRO NAV APPLICATION MANUAL
Page 18
•
On:
Unit that is regulating
PUMP
: status of the salt water pump (
OFF
,
tOn
,
On
)
COMp
: status of the compressor (
OFF
,
tOn
,
On
,
tOFF
)
The flashing numerical LED, within this menu, will remain on indicating the node that is being
monitored.
Remote unit configuration menu
By pressing the ESC+ENTER key for 3 seconds, enter a configuration menu protected by
password, which allows to display and configure the CAN addresses of the nodes and the
functioning hours of the compressor.
Adrr
: indicates the CAN address of the node
HCMp
: indicates the compressor hours of the unit
bAUd
: indicates the node baud
The flashing numerical LED, within this menu, will remain on indicating the node that is being
monitored.
Password
There are also three levels present protected by password. user, installer and administrator.
A password is associated to a level, which allows access to the various functionalities present in that
determined menu. Once the correct password has been entered, the protected functionalities will be
accessible.
Every level password can be modified only from the third level (administrator).
The range of values that can be set of the password is-999 / 9999.
After 4 minutes that no key is pressed, the password expires and must be set again.
Pressing the ENTER key for 3 seconds, requests the introduction of a password: by entering a
password correctly there are two effects:
⋅
release the correlated level
⋅
access to information the lower levels
Menu
The structure of the menus is the following:
⋅
User menu (Level 1)
o
Display and modification of regulation set points
⋅
Installer menu (Level 2)
o
Display and modification o the regulation parameters and alarm
⋅
Administrator menu (Level 3)
o
Modifying the password
o
Changing the unit of measurement
o
Modbus serial configuration parameters
Project and firmware versions
Press UP+DOWN at the same time for about 2 seconds and successively press ENTER on the InFo
label.
The information regarding the versions of the project and of the control firmware is displayed in
sequence, precisely:
Project Number <-> Project Version<-> Project Revision
Firmware Number <-> Firmware Version<-> Firmware Revision
use the UP and DOWN keys to scroll the information. Press ESC to return to the application pages.