4list of parameters, 1 list of the configuration parameters – EVCO c-pro nano NAV User Manual

Page 19

background image

C-PRO NANO AND MICRO NAV APPLICATION MANUAL

Page 19

4

List of parameters


Below find the list of all parameters managed by the application. A brief description, the range of
acceptable values, unit of measurement, the default value proposed and the menu in which it is
found is supplied for every parameter. The menus are structured following this logic:

LEV1: user menu

LEV2 : installer menu

LEV3 : administrator menu

4.1

List of the configuration parameters

Code

Parameter description

Default

Min

Max

U.

M.

Menu

Notes

USER PARAMETERS

SETC

Sets the value of the summer set point (chiller)

11.0

9.0

15.0

°C

LEV1

Note 1

SETH

Sets the value of the winter set point (heat
pump)

40.0

35.0

47.0

°C

LEV1

Note 1

RESt

Rests events log

0

0

1

LEV1

INSTALLER PARAMETERS

BndC

Sets the value of the regulation band for the
calculation of the enabling steps (chiller)

5.0

1.0

10.0

°C

LEV2

Note 1

BndH

Sets the value of the regulation band for the
calculation of the enabling steps (heat pump)

5.0

1.0

10.0

°C

LEV2

Note 1

tI

Integral time for the calculation of the
enabling steps

0

0

999

sec

LEV2

diFC

Sets the value of the summer differential
(chiller)

3.0

1.0

5.0

°C

LEV2

Note 1

diFH

Sets the value of the winter differential (heat
pump)

3.0

1.0

5.0

°C

LEV2

Note 1

dEL

Heat drop delta

5.0

3.0

7.0

°C

LEV2

Note 1

MInC

Output temperature operational limit (chiller)

6.0

5.0

8.0

°C

LEV2

Note 1

MInH

Output temperature operational limit (heat
pump)

46.0

45.0

48.0

°C

LEV2

Note 1

tOn

Minimum time for which the compressor must
remain on even if switch-off is requested

0

0

240

sec

LEV2

tOFF

Minimum time for which the compressor must
remain off even if switch-on is requested

120

0

999

sec

LEV2

nCMP

Maximum number of start-ups every hour

10

5

15

LEV2

tLP

Compressor switch-on low pressure alarm
delay

0

0

999

sec

LEV2

nLP

Number of interventions/hour for low pressure
alarm so that the alarm becomes manual

3

0

9

LEV2

t1

Flow alarm delay from the activation of the
regulation

30

0

t2

sec

LEV2

t2

Salt water pump alarm delay from the
activation of the regulation

60

t1

999

sec

LEV2

t3

Compressor command delay from the
activation of the salt water pump

15

0

999

sec

LEV2

t4

Fresh water pump switch-off delay during unit
change over or switch-off.

30

0

999

sec

LEV2

t5

Activation delay between different
compressors

10

0

999

sec

LEV2