C-PRO NANO AND MICRO NAV APPLICATION MANUAL

Page 26

6.6.2

Protection times

Below find a list of all times relative to management of the compressors
These times are used to protect the mechanical means from the various peaks to which they are
subjected.

tOn = Compressors minimum switch-on time. Once activated, the compressor will remain on for
this time before being able to be switched-off.

tOFF = Compressors minimum switch-off time.
Minimum time that must pass from the last switch-
off before the compressor can be switched-on again.

nCMP = Maximum number of compressor switch-ons in an hour.
Establishes a maximum number
of switch-ons during one hour: if this limit is reached, the regulator will wait for the conditions to
be present before switching the compressor on again.

t5 =Activation delay between different compressors. Minimum time between the activation of the
compressor of a unit after the last activation of a compressor of another unit.