EVCO c-pro nano NAV User Manual
Page 26

C-PRO NANO AND MICRO NAV APPLICATION MANUAL
Page 26
6.6.2
Protection times
Below find a list of all times relative to management of the compressors
These times are used to protect the mechanical means from the various peaks to which they are
subjected.
tOn = Compressors minimum switch-on time. Once activated, the compressor will remain on for
this time before being able to be switched-off.
tOFF = Compressors minimum switch-off time. Minimum time that must pass from the last switch-
off before the compressor can be switched-on again.
nCMP = Maximum number of compressor switch-ons in an hour. Establishes a maximum number
of switch-ons during one hour: if this limit is reached, the regulator will wait for the conditions to
be present before switching the compressor on again.
t5 =Activation delay between different compressors. Minimum time between the activation of the
compressor of a unit after the last activation of a compressor of another unit.