C-PRO NANO AND MICRO NAV APPLICATION MANUAL

Page 22

5

CONFIGURATIONS

5.1

Setting number of the slaves


To set the number of the slaves that will be connected to the master, hold the ENTER key for about
2 seconds and then access the main menu. Enter the administrator menu and modify the

nUM

parameter.

5.2

Setting addresses of the slaves


Procedure for setting the slave addresses (they leave the factory with the same configuration and
address equal to 1):

-

Power master

-

Connect only one slave unit at a time tot he master and power it

-

Press ENTER+ESC for 3 seconds

-

Select the node to be configured (it will always be node 1)

-

Select “Addr” from the node menu

-

Introduce the protection password

-

Sets the address of the unit as the most available address (address 4 if there are 4 units and
none yet configured, address 3 if there are 3 units and none yet configured, address 2 if there
are 4 units and two units already configured)

-

Repeat the operation for every slave unit excluding the first, which will maintain its own
default address at 1.

5.3

Setting baudrates of the slaves


Procedure for setting the baudRate (they leave the factory with the same configuration and equal to
20K):

-

Power master and slave and configure the addresses (see previous paragraph)

-

Press ENTER+ESC for 3 seconds

-

Select the node to be configured

-

Select “bAud” from the node menu

-

Introduce the protection password

-

Set the unit baud (20K, 50K, 125K, 500K) and remove it from the CAN network

-

Repeat the operation for every slave unit.

-

Once the operation has ended for the slave units, enter the master administrator parameters
and select the (Can) parameter to set the master baud

-

Re-connect all units to the network