C-PRO NANO AND MICRO NAV APPLICATION MANUAL
Page 22
5
CONFIGURATIONS
5.1
Setting number of the slaves
 
To set the number of the slaves that will be connected to the master, hold the ENTER key for about 
2 seconds and then access the main menu. Enter the administrator menu and modify the 
nUM
parameter. 
 
5.2
Setting addresses of the slaves
 
Procedure for setting the slave addresses (they leave the factory with the same configuration and 
address equal to 1): 
 
-
Power master
-
Connect only one slave unit at a time tot he master and power it
-
Press ENTER+ESC for 3 seconds
-
Select the node to be configured (it will always be node 1)
-
Select “Addr” from the node menu
-
Introduce the protection password
-
Sets the address of the unit as the most available address (address 4 if there are 4 units and 
none yet configured, address 3 if there are 3 units and none yet configured, address 2 if there 
are 4 units and two units already configured) 
-
Repeat the operation for every slave unit excluding the first, which will maintain its own 
default address at 1. 
5.3
Setting baudrates of the slaves
 
Procedure for setting the baudRate (they leave the factory with the same configuration and equal to 
20K): 
 
-
Power master and slave and configure the addresses (see previous paragraph)
-
Press ENTER+ESC for 3 seconds
-
Select the node to be configured
-
Select “bAud” from the node menu
-
Introduce the protection password
-
Set the unit baud (20K, 50K, 125K, 500K) and remove it from the CAN network
-
Repeat the operation for every slave unit.
-
Once the operation has ended for the slave units, enter the master administrator parameters 
and select the (Can) parameter to set the master baud 
-
Re-connect all units to the network