EVCO EVXS815P9 Installer manual User Manual

Page 39

background image

EVCO S.p.A.

EVSX815 | Installer manual ver. 1.3 | Code 144XS815E134

page 39 of 60

i6

0

1

- - - -

0

type of high pressure input 1

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i7

-1

240

s

5

high pressure alarm signalling delay (“HP” code)

-1 = the alarm will not be signalled

Par.

Min.

Max.

Unit

Default

Digital outputs

u1

0

1

- - - -

0

utility managed by the output K4 (14)

0 = door heating elements (in this case, parameter u5

will assume significance)

1 = condenser fan (in this case, parameter u5 will

assume significance)

u2

0

1

- - - -

0

enabling of cabinet light switch-on/off in manual mode

during "stand-by" status (15)

1 = yes

u5

-50.0

99.0

°C/°F (1)

20.0

cabinet temperature over which the door heating elements

are off (4)

u6

1

240

min

5

if parameter u11 is set at 1, maximum duration of needle

probe heating; see also parameter u7

if parameter u11 is set at 2, duration of UV light switch-on

for the sterilisation cycle

u7

-50.0

99.0

°C/°F (1)

40.0

needle probe heating end temperature (temperature

detected by the needle probe); see also parameter u6

u11

0

2

- - - -

0

utility managed by the output K5 (14)

0 = cabinet light (in this case, the DEEP FREEZING key

and parameters i0 and u2 will assume significance)

1 = needle probe heating (in this case, the DEEP

FREEZING key and parameters u6 and u7 will

assume significance)

2 = UV light (in this case, the DEEP FREEZING key and

parameter u6 will assume significance)

Par.

Min.

Max.

Unit

Default

Serial communication (MODBUS)

LA

1

247

- - - -

247

device address