beautypg.com

EVCO EVXS815P9 Installer manual User Manual

Page 31

background image

EVCO S.p.A.

EVSX815 | Installer manual ver. 1.3 | Code 144XS815E134

page 31 of 60

P0

0

1

- - - -

0

probe type

0 = PTC

1 = NTC

P1

0

1

- - - -

1

°C decimal point

1 = yes

P2

0

1

- - - -

0

temperature unit of measurement (2)

0 = °C

1 = °F

P3

0

1

- - - -

1

enabling the needle probe

1 = yes

P4

0

1

- - - -

1

enabling the evaporator probe

1 = yes

P8

0

250

ds

5

delay displaying temperature variation detected by the

probes

P9

- - - -

- - - -

- - - -

- - - -

reserved

Par.

Min.

Max.

Unit

Default

Main regulator

r0

0.1

15.0

°C/°F (1)

2.0

parameters differential r7, r8, r9, r10, r11 and r12

r1

1

500

min

90

duration of time-controlled blast chilling

r2

1

500

min

240

duration of time-controlled deep freezing

r3

-50.0

99.0

°C/°F (1)

3.0

temperature-controlled blast chilling end time temperature;

also end temperature of the temperature-controlled soft

deep freezing phase (temperature detected by the needle

probe); see also parameter r5

r4

-50.0

99.0

°C/°F (1)

-18.0

temperature-controlled deep freezing end temperature

(temperature detected by the needle probe); see also

parameter r6

r5

1

500

min

90

maximum duration of temperature-controlled blast chilling;

see parameter r3 also

r6

1

500

min

240

maximum

duration

of

temperature-controlled

deep

freezing; see parameter r4 also