EVSX815 | Installer manual ver. 1.3 | Code 144XS815E134

page 34 of 60

C0

0

240

min

0

minimum time between restoring the power supply after a

power cut, occurring during an operating cycle and

compressor switch-on

C1

0

240

min

5

minimum time between two consecutive compressor switch-

ons (3)

C2

0

240

min

3

minimum

time

between

compressor

switch-off

and

successive switch-on (3)

C3

0

240

s

0

compressor switch-on minimum duration

C4

0

240

min

10

duration of compressor switch-off during the cabinet probe

error (“Pr1” code) that occurs during storage; see also

parameter C5

C5

0

240

min

10

duration of compressor switch-on during the cabinet probe

error (“Pr1” code) that occurs during post blast chilling

storage; see also parameter C4

C9

0

240

min

30

duration of compressor switch-on during the cabinet probe

error (“Pr1” code) that occurs during post deep freezing

storage; see also parameter C4

Par.

Min.

Max.

Unit

Default

Defrosting (5)

d0

0

99

h

8

defrosting interval (6)

0 = defrosting will never be activated at intervals