8

COMPRESSOR OPERATING HOURS COUNT

8.1

Displaying compressor operating hours

Operate as follows:

1.

Make sure that the keyboard is not locked and that no procedure is in progress.

2.

Hold the DOWN key down for 1 s: the display will show the first label available.

3.

Press and release the UP or DOWN key to select “CH”.

4.

Press and release the BLAST CHILLING key: the display will show the compressor operating hours.

Operate as follows to exit the procedure:

5.

Press and release the BLAST CHILLING key or do not operate for 15 s: the display will show “Pb2” again.

6.

Press and release the UP or DOWN key until the display shows the magnitude indicated in paragraph 5.3 "The

display" or do not operate for 60 s.

8.2

Deleting the compressor operating hours

Operate as follows:

1.

Make sure that the keyboard is not locked and that no procedure is in progress.

2.

Hold the DOWN key down for 1 s: the display will show the first label available.

3.

Press and release the UP or DOWN key to select “rCH”.

4.

Press and release the BLAST CHILLING key: the display will show “0

5.

Press and release the UP or DOWN key within 15 s to set “149”.

6.

Press and release the BLAST CHILLING key or do not operate for 15 s: the display will show “- - - -” flashing for

4 s and the HACCP LED will switch off, after which the device will automatically exit the procedure and the

display will show the magnitude indicated in paragraph 5.3 “The display”.