beautypg.com

Troubleshooting – AERCO BMK 3.0 LN Nat. Gas APRIL 2009 User Manual

Page 62

background image

TROUBLESHOOTING

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

continued

3. Defective High Gas Pressure Switch



4. Gas pressure snubber not installed.

3. Remove the leads from the high gas pressure switch and

measure continuity across the common and normally closed
terminals with the unit not firing. Replace the switch if it does not
show continuity.

4. See Figure 8-1. Ensure that the gas pressure snubber is installed

at the high gas pressure switch.

HIGH WATER TEMP

SWITCH OPEN

1. Faulty Water temperature switch.

2. Incorrect PID settings.


3. Faulty shell temperature sensor.


4. Unit in Manual mode

5. Unit setpoint is greater than Over

Temperature Switch setpoint.

6. Boiler Management System PID or

other settings not correctly setup.

7. No interlock to boiler or BMS to

disable boiler(s) in event that system
pumps have failed.

8. System flow rate changes are

occurring faster than boilers can
respond.

1. Test the temperature switch to insure it trips at its actual water

temperature setting.

2. Check PID settings against Menu Default settings in the

Appendix. If the settings have been changed, record the current
readings then reset them to the default values.

3. Using the resistance charts in the Appendix C, Measure the

resistance of Shell sensor and BTU sensor at a known water
temperature.

4. If unit is in Manual Mode switch to Auto Mode.

5. Check setpoint of unit and setpoint of Temperature Switch;

Ensure that the temperature switch is set higher than the unit’s
setpoint.

6. Check the BMS for changes to PID default values, correct as

necessary.

7. If system pump is controlled by Energy Management System

other than BMS or pumps are individually controlled by boiler,
check to see if there are flow switches interlocked to the BMS or
boiler.

8. If the system is a variable flow system, monitor system flow

changes to ensure that the rate of flow change is not faster than
what the boilers can respond to.

HIGH WATER

TEMPERATURE

1. See HIGH WATER TEMPERATURE

SWITCH OPEN.

2. Temp HI Limit setting is too low.

1. See HIGH WATER TEMPERATURE SWITCH OPEN.

2. Check Temp HI Limit setting.

IGN BOARD

COMM FAULT

1. Communication fault has occurred

between the PMC board and
Ignition/Stepper (IGST) board

1. Press CLEAR button and restart unit. If fault persists, contact

qualified Service Personnel.

8

-6