MAINTENANCE

Table 7-1 - Maintenance Schedule

PARAGRAPH

ITEM

6 Mos.

12 Mos.

24 Mos.

Labor

Time

7.2

Spark

Igniter

*Inspect Inspect Replace 15

mins.

7.3

Flame

Detector

*Inspect Inspect Replace 15

mins.

7.4

Combustion

Calibration

*Check Check

1

hr.

7.5

Testing of

Safety

Devices

See CSD-1

Chart in

Appendix I

20

mins.

7.6 Burner

Inspect

2

hrs.

7.7

Condensate

Drain Traps

*Inspect

Inspect &

Clean

1

hr.

* Only performed after initial 6 month period after initial startup.

7.3 FLAME DETECTOR

The flame detector, part no. 66006, is located in
the body of the burner (see Fig. 7-1). The flame
detector may be HOT. Allow the unit to cool
sufficiently before removing the flame detector.

To inspect or replace the flame detector:

1. Set the ON/OFF switch on the control panel,

to the OFF position. Disconnect AC power
from the unit.

2. Remove the top panels from the unit.

3. Disconnect the flame detector lead wire.

Unscrew the flame detector and remove it.
(See Fig 7-2)

4. Inspect the detector thoroughly. If eroded,

the detector should be replaced. Otherwise
clean the detector with a fine emery cloth.

5. Reinstall the flame detector and flame

detector gasket, if removed.

6. Reconnect the flame detector lead wire.

7. Reinstall the side and top panels on the unit.

7.4 COMBUSTION CALIBRATION

Combustion settings must be checked at the
intervals shown in Table 7-1 as part of the
maintenance requirements. Refer to Chapter 4
for combustion calibration instructions.

SPARK

IGNITER

FLAME
DETECTOR

BURNER

HOUSING

Figure 7-2

Spark Igniter and Flame Detector

Location Cut-Away View

7-2