CONTROL PANEL OPERATING PROCEDURES

3.6 CONFIGURATION MENU

The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.

NOTE

The Configuration Menu settings shown in
Table 3-4 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.

Table 3-4. Configuration Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

Boiler or Water Heater

Boiler

Unit Size

0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
2.5 MBTU, 3.0 MBTU

1.0 MBTU

Boiler Mode

Constant Setpoint,

Remote Setpoint,

Direct Drive

Combination

Outdoor Reset

Constant

Setpoint

Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (BMS)

Network

4 – 20 mA,

1-5V

Bldg Ref Temp
(If Mode = Outdoor
Reset)

40°F 230°F 70°F

Reset Ratio
(If Mode = Outdoor
Reset)

0.1 9.9 1.2

Outdoor Sensor

Enabled or Disabled

Disabled

System Start Tmp
(If Outdoor Sensor =
Enabled)

30°F 100°F 60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

220°F

200°F

Temp Hi Limit

40°F

240°F

210°F

Max Fire Rate

40%

100%

100%

Pump Delay Timer

0 min.

30 min.

0 min.

Aux Start On Dly

0 sec.

120 sec.

0 sec.