beautypg.com

Installation, Ab b, Figure 2-5 condensate drain connection location – AERCO BMK 3.0 LN Nat. Gas APRIL 2009 User Manual

Page 14: 1 exhaust manifold condensate drain, 2 connecting manifold condensate drain, Figure 2-6 condensate trap installation

background image

INSTALLATION

2-4

SHELL DRAIN

VALVE

EXHAUST

MANIFOLD

REAR VIEW

A

A

B

B

CONDENSATE

TRAP

DRAIN

CONNECTING

MANIFOLD

DRAIN

UNIT

FRAME

CONNECTING

MANIFOLD

DRAIN

VALVE

CONDENSATE

DRAIN PIPE

TO

CONDENSATE

TRAP

SHELL

VIEW “B - B”

VIEW “A - A”

UNIT

FRAME

EXHAUST

MANIFOLD

CONDENSATE

TRAP

DRAIN

HOSE

CLAMP

1" I.D.
HOSE

TO FLOOR

DRAIN

Figure 2-5

Condensate Drain Connection Location

2.6.1 Exhaust Manifold Condensate
Drain

Refer to Figure 2-5, View A – A and install as
follows:

1. Connect a length of 1 inch I.D. hose (part no.

91030) to the drain on the connecting manifold
and secure it in place with a hose clamp.

2. Route the hose to a nearby floor drain.

2.6.2 Connecting Manifold Condensate
Drain

The connecting manifold drain pipe shown in
Figure 2-5, View B – B must be connected to a
separate condensate drain trap external to the
unit. Refer to Figure 2-6 and install the trap as
follows:

The condensate trap described in the
following steps can be installed on the
floor behind the unit as shown in Figure 2-
6. There will be sufficient downward slope
from the drain pipe to the trap inlet to
drain the condensate by gravity. Ensure
that the outlet hose from the trap slopes
away (down) from the trap.

1. Position the supplied condensate trap (part

no. 24060) on the floor at the rear of the
unit.

2. Install 3/4” NPT nipples in the tapped inlet

and outlet of the condensate trap.

3. Attach a length of 1½” I.D (part no. GM-

123352). hose between the connecting
manifold drain pipe and the inlet side of the
condensate trap (Figure 2-6). Secure both
ends of the hose with clamps.

4. Connect a second length of 1” I.D.

polypropylene hose to the outlet side of the
condensate trap and route it to a nearby floor
drain.

If desired, a Tee fitting may be used to connect the
two drain hoses from the exhaust manifold and the
outlet side of the of the condensate trap connected
in

If a floor drain is not available, a condensate pump
can be used to remove the condensate to drain.
The maximum condensate flow rate is 20 GPH.
The condensate drain trap, associated fittings and
drain lines must be removable for routine
maintenance. Therefore, DO NOT hard pipe.

Figure 2-6

Condensate Trap Installation