INITIAL START-UP

6. Adjust the fire rate to 0% by pressing the ▼

arrow key.

7. Ensure that the leak detection ball valve

downstream of the SSOV is open.

8. Set

the

ON/OFF switch to the ON position.

9. Change the fire rate to 29% using the ▲

arrow key. The unit should begin its start
sequence and fire.

10.

Next, verify that the gas pressure
downstream of the SSOV is 1.8” W.C. for
both FM and IRI gas trains. If gas pressure
adjustment is required, remove the brass
hex nut on the SSOV gas pressure regulator
(Figure 4-3). Make gas regulator adjust-
ments using a flat-tip screwdriver to obtain
1.8” W.C.

Figure 4-3

Regulator Adjustment Screw Location

11. Raise the firing rate to 100% and verify that

the gas pressure downstream of the SSOV
remains at 1.8” W.C. Readjust pressure if
necessary. -

12. With the firing rate at 100%, insert the

combustion analyzer probe into the flue
probe opening and allow enough time for the
combustion analyzer to settle.

13. Compare the measured oxygen level to the

oxygen range for the inlet air temperature
shown in Table 4-1. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values
shown.


Table 4-1

Combustion Oxygen Levels for a 100%

Firing Rate

Inlet Air

Temp

Oxygen %

± 0.2

Carbon

Monoxide

NOx

>100°F

4.8 %

<100 ppm

<30 ppm

90°F

5.0 %

<100 ppm

<30 ppm

80°F

5.2 %

<100 ppm

<30 ppm

<70°F

5.3 %

<100 ppm

<30 ppm



14. If necessary, adjust the iris air damper

shown in Figure 4-4 until the oxygen level is
within the range specified in Table 4-1.

15. Once the oxygen level is within the specified

range at 100%, lower the firing rate to 70%.

4-3