Control panel operating procedures – AERCO BMK 3.0 LN Nat. Gas APRIL 2009 User Manual
Page 27
CONTROL PANEL OPERATING PROCEDURES
3-5
3.4 OPERATING MENU
The Operating Menu displays a number of key
operating parameters for the unit as listed in
Table 3-2. This menu is “Read-Only” and does
not allow personnel to change or adjust any
displayed items. Since this menu is “Read-Only”,
it can be viewed at any time without entering a
password. Pressing the ▲ arrow key to display
the menu items in the order listed (Top-Down).
Pressing the ▼ arrow key will display the menu
items in reverse order (Bottom-Up).
3.5 SETUP MENU
The Setup Menu (Table 3-3) permits the
operator to enter the unit password (159) which
is required to change the menu options. To
prevent unauthorized use, the password will
time-out after 1 hour. Therefore, the correct
password must be reentered when required. In
addition to permitting password entries, the
Setup Menu is also used to enter date and time,
units of temperature measurements and entries
required for external communication and control
of the unit via the RS-232 port. A view-only
software version display is also provided to
indicate the current Control Box software
version.
NOTE
The Outdoor Temp display item shown with
an asterisk in Table 3-2 will not be displayed
unless the Outdoor Sensor function has
been enabled in the Configuration Menu
(Table 3-4).
Table 3-2. Operating Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Status Message
Active Setpoint
40°F
240°F
Aux Temp
30°F
245°F
Outdoor Temp*
-70°F
130°F
Fire Rate In
0%
Max Fire Rate
Flame Strength
0%
100%
Run Cycles
0
999,999
Run Hours
0
999,999
Fault Log
0
9
0
Table 3-3. Setup Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
0 9999 0
Language English
English
Time
12:00 am
11:59 pm
Date 01/01/00
12/31/99
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400, 4800, 9600, 19.2K
9600
Software
Ver 0.00
Ver 9.99