beautypg.com

Appendix d - indoor/outdoor reset ratio charts, Appendix d – AERCO BMK 3.0 LN Nat. Gas APRIL 2009 User Manual

Page 81

background image

APPENDIX D

D-1

APPENDIX D. - INDOOR/OUTDOOR RESET RATIO CHARTS


Table D-1. Header Temperature for a Building Reference Temperature of 50F

RESET RATIO

Air

Temp

0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4

50F

50 50 50 50 50 50 50 50 50 50

45F

53 54 55 56 57 58 59 60 60 62

40F

56 58 60 62 64 66 68 70 72 74

35F

59 62 65 68 71 74 77 80 83 86

30F

62 66 70 74 78 82 86 90 94 98

25F

65 70 75 80 85 90 95 100 105

110

20F

68 74 80 86 92 98 104 110 116

122

15F

71 78 85 92 99 106 113 120 127

134

10F

74 82 90 98 106 114 122 130 138 146

5F

77 86 95 104 113 122 131 140 149 158

0F

80 90 100 110 120 130 140 150 160 170

-5F

83 94 105 116 127 138 149 160 171 182

-10F

86 98 110 122 134 146 158 170 182 194

-15F

89 102 115 128 141 154 167 180 193 206

-20F

92 106 120 134 148 162 176 190 204 218


Table D-2. Header Temperature for a Building Reference Temperatrure of 60F

RESET RATIO

Air

Temp

0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4

60F

60 60 60 60 60 60 60 60 60 60

55F

63 64 65 66 67 68 69 70 71 72

50F

66 68 70 72 74 76 78 80 82 84

45F

69 72 75 78 81 84 87 90 93 96

40F

72 76 80 84 88 92 96 100

104

108

35F

75 80 85 90 95 100 105 110

115

120

30F

78 84 90 96 102 108 114 120 126 132

25F

81 88 95 102 109 116 123 130 137 144

20F

84 92 100 108 116 124 132 140 148 156

15F

87 96 105 114 123 132 141 150 159 168

10F

90 100 110 120 130 140 150 160 170 180

5F

93 104 115 126 137 148 159 170 181 192

0F

96 108 120 132 144 156 168 180 192 204

-5F

99 112 125 138 151 164 177 190 203 216

-10F

102 116 130 144 158 172 186 200 214

-15F

105 120 135 150 165 180 195 210

-20F

108 124 140 156 172 188 204