Troublesho oting – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 66

background image

TROUBLESHO

OTING

8

-

8

TABLE 8-1. BOILER TRO

UBLESHOOTING – Contin

ued

FAULT INDI

CATION

PROBABL

E CAU

SES

CORRECTI

VE ACTI

O

N

INTERL

OCK

OPEN

1.

Interlock jum

per not in

stall

ed or

remove

d

2.

Energy Man

ag

ement Syste

m

does

not have boil

er ena

bled.

3.

Device provin

g swit

ch ho

oked to

interloc

ks

is

not c

losed.

1.

Che

ck for a jumpe

r pro

pe

rly

ins

talled across

the interlock

terminals

in the I/O box

2.

If there are two external wi

res on the

se t

ermin

als

che

ck a

ny

Energy Man

ag

ement sy

ste

m

to

se

e if they have the units

disa

bled (a ju

mper may be

temporarily in

stalled to see

if the

interloc

k

ci

rc

uit is

func

tioning).

3.

Che

ck that proving switch f

or

any device

hooked to the interlo

ck

circuit is

closi

ng and that th

e device i

s op

eration

al.

LINE VOLTA

G

E

OUT OF P

H

ASE

1.

Line an

d Ne

ut

ral swit

che

d in AC

Power Box.

2.

Inc

orrec

t power s

upply trans

former

wirin

g.

1.

Che

ck Line (hot) and

Neut

ral in AC Power Box to ensure they

are not reversed

2.

Che

ck tran

sforme

r wi

ring,

in AC Powe

r Box, against the po

wer

box transfo

rm

er wi

ring di

ag

ram to en

sure it is wired

correctly

LOW GAS

PRESSURE

1.

In

co

rr

ec

t s

upp

ly g

as

p

re

ssu

re

.

2.

Defe

ctive Lo

w Pre

ssure

G

as Swit

ch

1.

Measure ga

s pre

ssure up

stream

of the supply gas

regulator w

ith

the unit firing. Ensure it is at leas

t 3.5”

W.C. for FM gas

train, or

4.0” W.

C. for IR

I gas

train. Max.

allowabl

e pre

ssure is 2 psig

(se

e pa

ra. 2.7.1).

2.

Measure ga

s pre

ssure at the lo

w ga

s pr

es

su

re swit

ch.

If

it is

greate

r than 2.6” W.

C., measure

cont

in

uit

y acro

ss t

he swit

ch

and re

pla

ce if nece

ssary.

LOW WATE

R

LEVEL

1.

Ins

uffic

ient water level in sys

tem

2.

Defective wat

er level ci

rcuitry.

3.

Defe

ctive wat

er level probe

.

1.

Che

ck sy

st

em

fo

r suf

ficie

nt

wat

er lev

el

.

2.

Test water le

vel circuitry u

sing the

Cont

rol Box front panel L

O

W

WATER TES

T

and RESE

T buttons. Repla

ce water

level

ci

rc

uitry if it does

not respond.

3.

Che

ck co

ntin

uity of probe end

to the sh

ell, chan

ge probe if there

is no continuit

y.

MODB

US COMM

FAULT

1.

Boiler n

ot seeing i

nform

ation from

Modbu

s net

work

1.

Che

ck net

w

or

k co

nne

ct

ion

s.

If

fault persi

sts, co

ntact q

ualified

Service Pe

rsonnel.

PRG SWTCH CLOSED

DU

RI

N

G

IG

N

ITI

ON

1.

A/F Valve rotated ope

n to purg

e and

did not rotate

to ignition pos

ition

1.

Start the u

ni

t. The Air/Fu

el Va

lve

sh

ould rotate to the purge

(ope

n)

po

sition, then

ba

ck to ig

nition

positio

n (to

w

ard

s

clo

sed

)

during the ignition c

yc

le. If the va

lve does

not rotate

back

to the

ignition po

sit

ion, che

ck the Air/Fuel

Valve cali

bration. If

calib

ration i

s okay, the pro

blem may be

in the Air/Fuel Valve or

the Control Box. Refer faul

t to qualified servi

ce pe

rso

nnel.