Aerco, Appendix g, Legend – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual
Page 110
APPENDIX G
G-4
NORTHVALE, NJ 07647
INTERNATIONAL, INC.
APPD.
DWN.BY
SCALE
DATE
DATE
SD
072606
AERCO
SD-A-691
C
REV.
BENCHMARK 3 MIL. BTU LOW NOx
GAS FIRED BOILER MULT. INSTALLATION
WITH ZERO SIDE CLEARANCE
5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.
2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN
4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6''
FROM BOILER
ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE
1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).
FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND
6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED
DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG.
P&T
AUTOMATIC
AIR VENT
AIR
SEPARATOR
1-1/2" NPT
DRAIN CONN.
HEIGHT 18'' ABOVE FLOOR.
3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.
BE 6'' AWAY FROM SIDE PANELS.
PRESSURE
REDUCING
FILL VALVE
DIAPHRAGM TYPE
EXPANSION TANK
BACKFLOW PREVENTER
LINE
SIZE
BYPASS
HEATING
SYSTEM
SUPPLY
SUPPLY
WATER
SYSTEM
PUMP
CHECK
VALVE
(TYP.)
* 2" MANUAL
SHUTOFF
VALVE
RELIEF
VALVE (TYP.)
ISOLATION VALVE
BALANCING VALVE
TEMPERATURE GAUGE
LEGEND
Y STRAINER
UNION
PRESSURE &
P&T
DRIP TRAP
7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN.
(SEE NOTE 7)
* CONDENSATE DRAIN TRAP
HEATING
SYSTEM
RETURN
P&T
GAS SUPPLY
P&T
P&T
8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE.
SEE DIAGRAM 1
* 2" MANUAL
SHUTOFF
VALVE
(TO BOILER)
Diagram 1
GAS SUPPLY
(SEE NOTE 8)
MAINTAIN A REGULATED
4" W.C. GAS PRESSURE
AT MAX BTU/HR INPUT
DRIP TRAP
NOTES:
AT MAXIMUM BTU/HR INPUT,
MAINTAIN MINIMUM NATURAL GAS PRESSURE AT
3.5" W.C. (FM GAS TRAIN)/4.0" W.C. (IRI GAS TRAIN)
MAX GAS PRESSURE = 2.0 PSIG.
(SEE NOTE 6)