beautypg.com

Installation – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 21

background image

INSTALLATION

2-9

an enable/disable outdoor temperature, see the

Configuration menu in Chapter 3.
The outdoor sensor may be wired up to 200 feet

from the boiler. It is connected to the OUTDOOR

SENSOR IN and SENSOR COMMON terminals

in the I/O Box (see Figures 2-10 and 2-11). Wire

the sensor using a twisted shielded pair wire

from 18 to 22 AWG. There is no polarity to

observe when terminating these wires. The

shield is to be connected only to the terminals

labeled SHIELD in the I/O Box. The sensor end

of the shield must be left free and ungrounded.
When mounting the sensor, it must be located

on the North side of the building where an

average outside air temperature is expected.

The sensor must be shielded from direct sunlight

as well as impingement by the elements. If a

shield is used, it must allow for free air

circulation.

2.10.2 AIR SENSOR IN

The AIR SENSOR IN is connected to the AUX

SENSOR IN and SENSOR COMMON terminals

on the I/O board. The AIR SENSOR measures

the temperature of the air input to the Air/Fuel

Valve. This temperature reading is one of the

components used to calculate the rotational

speed of the blower used in the combustion

Calibration process (Chapter 4).
The AUX SENSOR IN terminals can be used to

add an additional temperature sensor for

monitoring purposes. This input is always

enabled and is a view-only input that can be

seen in the Operating Menu. The sensor must

be wired to the AUX SENSOR IN and SENSOR

COMMON terminals and must be similar to

AERCO BALCO wire sensor Part No. 12449. A

resistance chart for this sensor is provided in

Appendix C.

2.10.3 ANALOG IN

The ANALOG IN + and – terminals are used

when an external signal is used to drive the

firing rate (Direct Drive Mode) or change the

setpoint (Remote Setpoint Mode) of the Boiler.
Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA

/ 0 to 5 VDC signal may be used to vary the

setpoint or firing rate. The factory default setting

is for 4 to 20 mA / 1 to 5 VDC, however this may

be changed to 0 to 20 mA / 0 to 5 VDC using the

Configuration Menu described in Chapter 3. If

voltage rather than current is selected as the

drive signal, a DIP switch must be set on the

PMC Board located inside the Control Box.

Contact the AERCO factory for information on

setting DIP switches.

All of the supplied signals must be floating

(ungrounded) signals. Connections between the

signal source and the Boiler’s I/O Box must be

made using twisted shielded pair wire from 18 to

22 AWG, such as Belden 9841 (see

Figure 2-11). Polarity must be maintained. The

shield must be connected only at the source end

and must be left floating (not connected) at the

Boiler’s I/O Box.
Regardless of whether voltage or current is used

for the drive signal, they are linearly mapped to

a 40°F to 240°F setpoint or a 0% to 100% firing

rate. No scaling for these signals is provided

2.10.4 B.M.S. (PWM) IN

NOTE

Only BMS Model 168 can utilize Pulse

Width Modulation (PWM), not the BMS II

(Model 5R5-384).

These terminals are used to connect the

AERCO Boiler Management System (BMS)

Model 168 to the unit. The BMS Model 168

utilizes a 12 millisecond, ON/OFF duty cycle.

This duty cycle is Pulse Width Modulated (PWM)

to control firing rate. A 0% firing rate = a 5% ON

pulse and a 100% firing rate = a 95% ON pulse.

2.10.5 SHIELD

The SHIELD terminals are used to terminate any

shields used on sensor wires connected to the

unit. Only shields must be connected to these

terminals.

IMPORTANT

DO NOT USE the mA OUT output to

remotely monitor Setpoint, Outlet Temp or

Fire Rate Out.

2.10.6 mA OUT

These terminals provide a 4 to 20 mA output to

the VFD (if so equipped) to control the rotational

speed of the blower. This function is enabled in

the Configuration Menu (Chapter 3, Table 3-4).

2.10.7 0 – 10V OUT

These terminals provide a 0 to 10V output to

control the rotational speed of the blower. This

function is enabled in the Configuration Menu

(Chapter 3, Table 3-4).

2.10.8 RS-485 COMM

These terminals are used for RS-485 MODBUS

serial communication between the unit and an

external “Master” such as a Boiler Management

System (BMS), Energy Management System

(EMS), Building Automation System (BAS) or

other suitable device.