beautypg.com

Safety device testing – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 50

background image

SAFETY DEVICE TESTING

6-4

3. Close the manual gas shutoff valve located

between the Safety Shut-Off Valve (SSOV)
and the Air/Fuel Valve (see Figure 6-3).

MANUAL GAS

SHUTOFF VALVE

HANDLE

SSOV

AIR

INLET

AIR/FUEL

VALVE

BLOWER

GAS

INLET

PARTIAL LEFT SIDE VIEW

P/O FRAME

BLOCKED

INLET

SWITCH

BLOWER PROOF

SWITCH

Figure 6-3

Manual Gas Shut-Off Valve Location

4. Set the ON/OFF switch to the ON position to

start the unit.

5. The unit should shut down after reaching the

Ignition cycle and display FLAME LOSS
DURING IGN.

6. Open the valve previously closed in step 3

and press the CLEAR button.

7. Restart the unit and allow it to prove flame.

8. Once flame is proven, close the manual gas

valve located between the SSOV and the
Air/Fuel Valve.

9. The unit should shut down and display

FLAME LOSS DURING RUN.

10. Open the valve previously closed in step 8.

11. Press the CLEAR button. The unit should

restart and fire.

6.8 AIR FLOW FAULT TESTS

These tests check the operation of the Blower
Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.

1. Disable the blower output drive voltage as

follows:

(a) Press the MENU key until CONFIGUR-

ATION MENU is displayed.

(b) 3UHVV WKH Ÿ DUURZ NH\ XQWLO WKH ANA-

LOG OUTPUT function is displayed,
then press the CHANGE key.

(c) 3UHVV WKH ź DUURZ NH\ XQWLO OFF is

displayed, then press the ENTER key.

2. Start the unit in the Manual Mode at a valve

position between 25% and 30%.

3. The unit should shut down and display

AIRFLOW FAULT DURING PURGE.

4. Re-enable the blower output drive voltage by

performing the following steps:

(a) Press the MENU key until CONFIGUR-

ATION MENU is displayed.

(b) 3UHVVWKHŸDUURZNH\XQWLOWKHANA-

LOG OUTPUT function is displayed,
then press the CHANGE key.

(c) 3UHVVWKHŸDUURZNH\XQWLOVALVE

POSITION 0-10V is displayed, then
press the ENTER key.


5. Once the unit has proved flame, turn off the

blower by going to the Configuration Menu,
Analog Output menu item and select OFF.

6. The Blower Proof Switch will open and the

blower should stop. The unit should shut
down and display AIRFLOW FAULT
DURING RUN
.

7. Go to the Configuration Menu, Analog Output

item and select Valve Position 0-10v.

8. Press the CLEAR button. The unit should

restart.

9. Next, check the Blocked Inlet Switch by first

noting the current position of the Iris Air
Damper and then closing the Damper to
position 8.