Aerco, Appendix g, Legend – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual
Page 107

APPENDIX G
G-1
AIR
SEPARATOR
AUTOMATIC
AIR VENT
LINE
SIZE
BYPASS
BACKFLOW PREVENTER
DIAPHRAGM TYPE
EXPANSION TANK
WATER
SUPPLY
PRESSURE
REDUCING
FILL VALVE
CHECK
VALVE
(TYP.)
HEATING
SYSTEM
SUPPLY
SYSTEM
PUMP
P&T
RELIEF
VALVE (TYP.)
HEATING
SYSTEM
RETURN
AT MAXIMUM BTU/HR INPUT,
MAINTAIN MINIMUM NATURAL GAS PRESSURE AT
3.5" W.C. (FM GAS TRAIN)/4.0" W.C. (IRI GAS TRAIN)
MAX GAS PRESSURE = 2.0 PSIG.
(SEE NOTE 6)
* 2" MANUAL
SHUTOFF
VALVE
GAS SUPPLY
TEMPERATURE GAUGE
P&T
PRESSURE &
BALANCING VALVE
ISOLATION VALVE
UNION
Y STRAINER
LEGEND
AERCO
SD
MC
BENCHMARK 3 MIL. BTU LOW NOx
SINGLE UNIT INSTALLATION
SCALE
DWN.BY
APPD.
SD-A-681
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
061506
DATE
DATE
GAS FIRED BOILER
REV.
C
DRIP TRAP
* CONDENSATE DRAIN TRAP
1-1/2" NPT
DRAIN CONN.
DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG.
6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND
FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A
1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-802).
ELECTRIC CONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE
4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER
2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN
5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.
BE 6'' AWAY FROM SIDE PANELS.
3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.
HEIGHT 18'' ABOVE FLOOR.
NOTES:
7) EACH CONDENSATE PORT CAN BE PIPED INDIVIDUALLY TO MAIN DRAIN.
(SEE NOTE 7)
DRIP TRAP
GAS SUPPLY
* 2" MANUAL
SHUTOFF
VALVE
Diagram 1
8) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS, REGARDLESS OF SUPPLY PRESSURE,
SEE DIAGRAM 1
MAINTAIN A REGULATED
3.5" W.C. (NAT. GAS, FM/
4.0" W.C. (NAT. GAS, IRI/GAS
PRESSURE AT MAX BTU/HR INPUT
(TO BOILER)
(SEE NOTE 8)