Initial start-up – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 36

background image

INITIAL START-UP

4-2

4. Install a NPT-to-barbed fitting into the

tapped plug port.

5. Attach one end of the plastic tubing to the

barbed fitting and the other end to the 16

inch W.C. manometer.

TO

AIR/FUEL

VALVE

GAS

INLET

SSOV

1/8" NPT PLUG

(INSTALL MANOMETER HERE)

HIGH GAS

PRESSURE

SWITCH

LEAK DETECTION

BALL VALVE

LOW GAS

PRESSURE

SWITCH

Figure 4-1.

1/8 Inch Gas Plug Location

4.2.3 Accessing the Vent Probe Port

The unit contains NPT plugs on both the left and

right side of the exhaust manifold at the rear of

the unit as shown in Figure 4-2.

UNIT

FRAME

EXHAUST

MANIFOLD

CONDENSATE

TRAP

DRAIN

HOSE

TO FLOOR

DRAIN

FLUE

VENT PROBE

PORT

Figure 4-2

Analyzer Probe Hole Location

Prepare the port for the combustion analyzer

probe as follows:
1. Remove the plug from the probe port on the

left or right side of the exhaust manifold.

2. If necessary, adjust the stop on the

combustion analyzer probe so that it will

extend mid-way into the flue gas flow. DO

NOT install the probe at this time.

4.3 NATURAL GAS COMBUSTION

CALIBRATION

The Benchmark 3.0LN Boiler is combustion

calibrated at the factory prior to shipping.

However, recalibration as part of initial start-up

is necessary due to changes in the local altitude,

gas BTU content, gas supply piping and supply

regulators. Factory Test Data sheets are

shipped with each unit. These sheets must be

filled out and returned to AERCO for proper

Warranty Validation.
It is important to perform the following procedure

as outlined. This will keep readjustments to a

minimum and provide optimum performance.
1. Open the water supply and return valves to

the unit and ensure that the system pumps

are running.

2. Open the natural gas supply valve(s) to the

unit.

3. Set the control panel

ON/OFF switch to the

OFF position.

4. Turn on external AC power to the unit. The

display will show LOSS OF POWER and the

time and date.

5. Set the unit to the Manual Mode by pressing

the

AUTO/MAN key. A flashing Manual

Valve Position message will be displayed

showing the present air/fuel valve % open

position. Also, the

MANUAL LED will light.

6. Adjust the air/fuel valve position to 0% by

pressing the ▼ arrow key.

7. Ensure that the leak detection ball valve

downstream of the SSOV is open.

8. Set the

ON/OFF switch to the ON position.

9. Change the valve position to 29% using the

▲ arrow key. The unit should begin its start

sequence and fire.