HV-G/HW-G Series

Page 41

12. Full/Dribble Batch Function

Caution

The comparison of the full/dribble batch function can not be restored. (One
way sequence). If the weight value becomes less than the final value after the
value reached a predetermined target value, neither HI nor LO is on.

The parameters of the upper limit value (HI) and the final value (HI) use the
same memory. The parameters of the lower limit value (LO) and the
preliminary value (OK) use the same memory.

The upper/lower comparator function, the simple batch function and the

full/dribble batch function can not be used at the same time because these
parameters use the common memory.

Set the zero band greater than the tare value.


Operation

The batch process starts when the

SET

key is pressed.

When a parameter from

f10 0

or

f10 2

of the full/dribble batch sub-function is

selected, the F key functions as the finish key.


Parameter List and Word Definition

The "gross" is a total weight value (the tare value is not subtracted).
The "net" is a measurement value with the tare value subtracted from the gross.
The "zero band" means the zero detection level.
The "zero point" is the fundamental starting point to weigh anything.

Comparator

Function table

Description

A

f6 9

Full/dribble batch function.

A

Full/dribble batch sub-function

Function table

Description

A

f10 0

When the

F

key is pressed after final value is reached, the current

process is finished.

A
A

f10 1

When the stability mark is displayed after final value is reached,
the current process is finished.

A
A

f10 2

When the

SET

key is pressed, the scale automatically tares and

starts the full/dribble batch process. When the

F

key is pressed

after final value is reached, the current process is finished.

A
A
A

f10 3

When the

SET

key is pressed, the scale automatically tares and

starts the full/dribble batch process. When the stability mark is
displayed after final value is reached, the current process is
finished.

A
A
A

Hold

Function table

Description

A

f12 0

The hold function is not used.

A