Types of error and error code, Types of error and error, 1 troubleshooting – KEYENCE DL-PD1 User Manual
Page 67: Appe ndi x
4-1
Troubleshooting
4-3
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (IG) -
Appe
ndi
x
4
Types of error and error code
For how to read error information using a diagnosis function, refer to "Device maps"
(page 3-18).
Slot
Error code
(DEC)
Description
Solution
0
(DL-PD1)
16
Unassigned ID error
The number of sensor amplifiers increased during
operation. Check the connection with the sensor
amplifier.
17
Start-time Communication error
Check the connection with the sensor amplifier
and cycle the power.
18
Unsupported Sensor Connection
error
There is connected a sensor amplifier of a model
incompatible with the DL-PD1. Connect a sensor
amplifier of a compatible model.
19
Mixed Model error
A foreign sensor amplifier (i.e., one that cannot be
intermixed) is connected. Remove the foreign
sensor amplifier.
20
Start-time Communication error
Check the connection with the sensor amplifier
and cycle the power.
21
Current Limitation error
The current limitation exceeds the allowable
range. Check the allowable range of the number of
the sensor amplifiers.
22
Communication error between
Sensors
An error exists in the communication between
sensor amplifiers. Check the connections of the
sensor amplifiers, and then turn off the power and
back on.
23
Changed Station Address error
The station address was changed during
operation. If it was not an intentional change,
check the correct station address and set.
24 to 31
Reserved for system
00
No error
-
1-4
(Sensor
amplifier)
16
Overcurrent error
Refer to the IG series user's manual.
17
EEPROM error
18
Head error
19
T/R reverse connection error
20
Receiver EEPROM error
21
Receiver error
22
Transmitter error
23
Transmitter laser error
24
Model mismatch error
25
Head error (standard waveform)
26
Standard waveform error 1-4
27
Communication error
28
Additional setting error
29
Calculation error
30 to 31
Reserved for system
00
No error
-