2 filter on the weight – Rice Lake SCT-10 User Manual
Page 23

Configuration 19
2.2
Filter On The Weight
The filtering selection is used to eliminate environment noise, and is typically a
compromise between responsiveness and stability. The lower the number, the
more responsive the display will be to weight changes. The filter is used to
stabilize a weight as long as the variations are smaller than the corresponding
“Response Time”. The filter setting is dependent on the type of application and
the required update rate.
Setting this parameter allows a stable weight display to be obtained. To increase
the effect (weight more stable), increase the value.
1. Press and hold
, then press
. CALIb will be displayed.
2. Press
or
until FILtEr is displayed, press
. LED’s will
begin scrolling.
3. Press
or
until desired filter value is displayed, press
.
4. The weight is displayed (all LED’s will be flashing) and the displayed
stability can be experimentally verified. Press
.
5. If stability is not satisfactory, press
, this returns indicator to FILtEr
option and the filter may be modified again until an optimum result is
achieved.
6. Press
to exit set-up menu.
The filter enables to stabilize a weight as long as its variations are
smaller than the corresponding “Response Time”. It is necessary
to set this filter according to the type of application and to the full
scale value set.
Filter Value
Response times
[ms]
Display and serial port refresh frequency
[Hz]
0
80
80
1
190
80
2
260
40
3
450
26
4*
900
13
5
1700
13
6
2500
13
7
4200
10
8
6000
10
9
7500
5
* indicates default value.
Table 2-4. Filter Settings