beautypg.com

Warning, Operating your furnace, Electric power supply – Qmark CFWF - Counterflow Electric Wall Furnace User Manual

Page 8: Junction box, Electrical connection, Grounding, Low voltage connections, Figure 11

background image

Electric Power Supply

Your Counterflow Wall Furnace requires a 240-volt, 60

cycle, 40-ampere circuit from a separate circuit breaker or

fuse in your service panel. Do not run supply wires inside

the furnace cabinet, except from the top of the cabinet

down to the junction box.

Junction Box

Power supply connections are made inside the junction

box located in the upper end of the cabinet. See Fig. 11

and Fig. 1, page 2.

Electrical Connection

Connect 240V conduit to top of furnace as shown in Fig.

11. Pull supply wires through conduit and into junction

box. Attach 240V supply wires to "LINE" connection at

terminal board. Refer to wiring diagram on junction box

cover plate. If you do not feel comfortable doing this, or

have any doubts

how to comply with code, consult your electrical inspector

or a licensed electrician.

Grounding

Provide ground connection from the unitʼs terminal board

to a grounded connection in the electrical service panel or

a properly driven and electrically grounded ground rod.

Low Voltage Connections

Run thermostat wire to the furnace. See THERMOSTAT

INSTALLATION, page 6.

Connect the thermostat wires to the two (thermostat)

wires extending inside the junction box. Refer to wiring

diagram on junction box cover plate and Fig. 11.

When furnace mounting has been completed, see steps

1, 2, and 3 below.

Refer to Fig. 1, page 2.

1. Replace junction box cover plate. Tighten screws

securely.

2. Replace bottom front panel

3. Replace top front panel.

Note: For supply connections use 6 AWG or larger wires

suitable for at least 60 C (140 F). Use copper wire only.

Operating Your Furnace

This heater is controlled by a 24-volt wall thermostat that

is included. Set the thermostat to a higher temperature

than you think will be comfortable. Let the heater run and

when the room reaches a comfortable temperature, adjust

the dial counter-clockwise slowly until the heater cuts off.

The thermostat will maintain this temperature.

This heater is equipped with an automatic reset over-tem-

perature device. This device cuts the heater off if it should

operate at an abnormal temperature. Also, a pilot light

located on the top right of the fan panel (visible through

the grille) will come on. When the heater cools back down

to a normal level, the automatic reset will restore opera-

tion and the pilot light will turn off.
Additionally, your heater is equipped with micro temp heat

limits ("one-shots") to protect against excessive and pro-

longed current surges. If these device(s) open(s) the

heating circuit, the limit(s) must be replaced by a qualified

Service Technician, who will also determine and correct

the cause of failure.

Air volume may be adjusted if you have installed the

CFWFRO rear grille. Do not attempt to reduce the flow

of air from the front grille. Doing so will cause the limit

devices to shut down the heater. Do not obstruct the front

grille (or rear grille, if so equipped).

TO THERMOSTAT

CONDUIT

ELECTRICAL SUPPLY

WIRES-240V

SEE WIRE

CONNECTION

DIAGRAM

ABOVE

TO APPROVED

GROUND

TERMINAL

BOARD

LINE 1

GND.

LINE 2

JUNCTION

BOX

Figure 11

NOTE: ALL WIRING NOT SHOWN

8

If this light comes on this means your

heater has operated abnormally. Check for

air blockages and remove. If this does not

solve your problem, call a qualified

Service Technician.

WARNING

!