beautypg.com

Cut wall openings, Electrical supply rough-in, Figure 3 figure 4 – Qmark CFWF - Counterflow Electric Wall Furnace User Manual

Page 4: Figure 5

background image

Note: IF STUDS ARE NOT ON 16-INCH (406 mm) CEN-

TERS, SEE CLOSE OFF STUD SPACE ON PAGE 4 AND

5.

Cut Wall Openings

Refer to Figure 3. Lay out and cut the required opening

in wall.

The vertical height given includes an allowance of 3 inch-

es (76 mm) extra to allow room for wiring after the furnace

is installed.

Electrical Supply Rough-In

1. Make entry holes in the ceiling wall plate above the fur-

nace to route the conduit, electrical power supply

wires, and the thermostat wiring to the furnace.

2. If this is impractical, entry holes 1 inch (25 mm) for

electrical conduit and 1/2 inch (13 mm) for thermostat

wire may be drilled through either wall stud above the

furnace and the wiring may be routed from an adjoin-

ing stud space. You may also route the wiring from the

crawl space or basement to a point above the furnace

to match the openings in Fig. 4.

3. Install conduit so that it extends 4 inches (102 mm)

below the top of the furnace wall opening. One (1)

inch (25 mm) of conduit should extend inside the fur-

nace cabinet (See Fig. 3).

Note: Flexible conduit may be used only if it meets local

codes and ordinances.

1. The electrical supply wires, ground wire, and the ther-

mostat wires may now be routed to the furnace loca-

tions. See THERMOSTAT INSTALLATION, pages 6,

and ELECTRICAL WIRING page 8.

2. Ensure that there is enough wire at the furnace to

make the connections inside the furnace junction box.

Close Off Stud Space (If Necessary)

If studs are not on 16 inch (406 mm) centers, cut the hole

for the Counterflow Wall Furnace next to an existing stud

and frame in the other side using a 2x4 (or other lumber

as required) and spacer blocks or shims. See Fig. 5.

CL

Figure 3

Figure 4

FLEXIBLE

CONDUIT

FINISHED

FLOOR

6”

4”

14-3/8”

(365mm)

12-1/4”

(311mm)

71-1/2”

(1816mm)

75-1/2”

(1905mm)

8-1/4”

(210mm)

3-3/4”(95mm)

WALL CUTOUT

FOR OPTIONAL

REAR OUTLET

CENTERED

BETWEEN STUDS

12”

8”

(203mm)

4-7/8”

OPTIONAL REAR

OUTLET CUTOUT

MARKS

FINISHED FLOOR

6-5/8”

168 mm

72-1/2”

(184cm)

BACK

FRONT

SIDE

14-1/8”

7”

6-1/8”(156mm)

24V THERMOSTAT WIRE ENTRY

3/4” (19 mm) CONDUIT ENTRY

FRONT

1/2”

18-3/8”

(467mm)

2”

8”

2-1/4” (57mm)

6-1/8”

(156 mm)

(203mm)

(50 mm)

(359mm)

(13mm)

(305 mm)

(124 mm)

(102mm)

(152mm)

4

Figure 5

CEILING

PLATE

2X4 BACKING

IF MORE THAN

18” BETWEEN

TOP OF

CUTOUT &

CEILING LATE

EXISTING STUD

FLOOR PLATE

14-3/8”

(365mm)

SPACER

BLOCK AS

REQUIRED

NEW STUD

EXISTING STUD

(179mm)