Type rp2 & rs2 2 element infrared heaters, Installation instructions, Save these instructions
Read Carefully – This instruction sheet contains vital informa-
tion for the proper installation, use, and efficient operation of the
heater described. Carefully read this manual before installa-
tion, cleaning, or operation of the heater. Failure to adhere to
the instructions could result in fire, electrical shock, death, seri-
ous personal injury, or property damage. Save these instruc-
tions and review frequently for continuing safe operation and
instructing future users.
CAUTION – TO REDUCE RISK OF FIRE AND ELEC-
TRIC SHOCK:
1. Disconnect all power coming to the heater at main service
panel before wiring, installing elements, servicing, or disas-
sembling heater.
2. All wiring must be in accordance with local and National
Electrical Codes and the heater must be grounded as a pre-
caution against possible electrical shock.
3. Verify the power supply voltage coming to the heater match-
es the rating printed on the heater nameplate before ener-
gizing.
4. Supply wire coming to the heater must be rated at least 90
degrees C. USE COPPER WIRE ONLY.
5.Minimum clearances, as specified in Figure 1, must be main-
tained. Keep combustible material, such as boxes, crates,
etc., away form heater.
6. This heater is not suitable for use in hazardous locations as
described by the NFPA. Do not use in areas where paint,
gasoline, or other flammable liquids are used or stored.
7. Do not use TYPE RP heaters in areas where corrosive
agents are present, such as marine, green houses, or chem-
ical storage areas. TYPE RS heaters are better suited for
these applications.
8. The mounting structure and anchoring hardware must be
capable of reliably supporting the total weight of the heater
and all accessories used.
See selection chart for heater
weight.
9. This heater is intended for ceiling mounting (or wall mount-
ing, with accessory –WMB Wall Mounting Bracket) only.
Elements must be horizontal.
FIXTURE SELECTION CHART
( Enclosure only - Select Appropriate Element from Element Selection Chart )
Type RP2 & RS2
2 Element
Infrared Heaters
Installation Instructions
WARNING
!
SAVE THESE INSTRUCTIONS
REFLECTOR DESIGN
DIMENSIONS
30 DEG.
60 DEG.
90 DEG.
HEIGHT
WIDTH
LENGTH
WT.
ENCLOSURE
SYMMETRICAL ASYMMETRICAL
SYMMETRICAL
ASYMMETRICAL
SYMMETRICAL
in. (mm)
in. (mm)
in. (mm)
lbs. (kg)
PAINTED STEEL
RP223SA
RP223ASA
RP226SA
RP226ASA
RP229SA
24 (610)
19 (8.6)
STAINLESS STEEL
RS223SA
RS223ASA
RS226SA
RS226ASA
RS229SA
PAINTED STEEL
RP233SA
RP233ASA
RP236SA
RP236ASA
RP239SA
7.125 (181) 15 (381)
33 (838)
24 (10.9)
STAINLESS STEEL
RS233SA
RS233ASA
RS236SA
RS236ASA
RS239SA
PAINTED STEEL
RP243SA
RP243ASA
RP246SA
RP246ASA
RP249SA
46 (1168) 31 (14.1)
STAINLESS STEEL
RS243SA
RS243ASA
RS246SA
RS246ASA
RS249SA