beautypg.com

Surface mount installation, Thermostat installation, Caution – Qmark CFWF - Counterflow Electric Wall Furnace User Manual

Page 5

background image

In some high ceilings the distance from the top of the

cutout to the ceiling wall plate may be more than 18 inch-

es (457 mm). If so, we recommend that you close off this

space. Nail a 2x4 horizontally between the studs to close

off this space. Drill entry holes in this as required.

Surface Mount Installation

If you are using the optional rear outlet (CFWFRO), refer

to Optional Rear Outlet Installation on page 7 before pro-

ceeding.

Locate Wall Studs

Use a stud locator or small finishing nails. Drive and

remove a small finishing nail through the wall surface until

you find a stud. Then locate the side of the stud using the

same technique. Leaving that locating nail there, locate

the other side of the stud. Once you have done this, you

should be able to easily locate the next stud. The inside

edge of the next stud should be approximately 14-1/2

inches (368 mm) from the one you just found.

Cut Wall Opening

If you are using the optional rear outlet (CFWFRO), cut

the 8-1/4 (210 mm) inch by 12-1/4 inch (311 mm) opening

ONLY as shown in Fig. 3, page 4. Refer to Optional Rear

Outlet Installation on page 7 before proceeding.

1. If impractical to route the wiring to the furnace from the

attic, entry holes 1 inch (25 mm) for electrical conduit

and 1/2 inch (13 mm) for thermostat wire may be

drilled through either wall stud above the furnace and

the wiring may be routed from an adjoining stud space.

You may also route the wiring from the crawl space or

basement to a point above the furnace to match the

openings in Fig. 4.

2. To route the conduit, electrical power supply wires, and

thermostat wires to the furnace top, entry holes must

be made in the wallboard above the furnace location.

3. Electrical supply opening must be located at 2 inches

(51 mm)above the furnace top to match opening

shown in Fig. 4., page 6.

4. Drill a 1-inch (25 mm) hole for the electrical supply

wiring and a 1/2 inch (13 mm) hole for the thermostat

wires at the selected locations.

5. Route the flexible conduit to the 1 inch (25 mm) hole in

the wallboard and allow 1 inch (25 mm) to extend

below the furnace top (71-1/2 inches [1816 mm] from

the finished floor). See Fig. 3, page 4.

6. You may now route the electrical supply wires, ground

wire, and the thermostat wires to the furnace locations.

See THERMOSTAT INSTALLATION, pages 6, and

ELECTRICAL WIRING page 9.

Thermostat Installation

1. Thermostat cable must be run to the location selected.

All wiring must agree with the local codes and ordi-

nances. These instructions describe how to wire the

thermostat from the attic but it can also come from the

basement or crawl space.

2. Locate the thermostat and then drive a small nail hole

through the ceiling in the corner of the wall and ceiling

above the thermostat location. Pull out the nail and

push a small stiff wire through the hole to locate the

wire in the attic. Drill a 1/2 inch (13 mm) hole through

the ceiling wall plate.

3. Using the stiff wire, probe for obstructions in the wall.

Then drill 1/2 inch (13 mm) hole through the wall at the

selected location for the thermostat.

4. Feed the thermostat cable from the ceiling into the

wall. Snag the thermostat cable through the hole and

pull through so that 6 inches (152 mm) of cable pro-

trudes.

5. Route cable to Counterflow Wall Furnace.

CAUTION

!

To avoid electrical shock, turn off electrical

circuits that run through the wall where you

are installing the furnace.

Route Thermostat Cable

SMALL

FINISH

NAIL TO

LOCATE

HEADER

THERMOSTAT

CABLE

STIFF WIRE TO

SNAG CABLE

5

Figure 6