Error Code
Message Information
3.
PSU0035
Message
An over voltage fault detected on power supply <number>.
Action
Check input power or reinstall the power supply. If the issue
persists, see
PSU0036
Message
An over current fault detected on power supply <number>.
Details
This failure may be the result of an electrical issue with
cables or subsystem components in the system.
Action
1.
Remove and reinstall the power supply.
2.
Check cables and subsystem components in the system
for damage.
3.
PSU0037
Message
Fan failure detected on power supply <number>.
Action
Check for fan blockage. If the problem persists, see
.
PSU0076
Message
A power supply wattage mismatch is detected; power supply
<number> is rated for <value> watts.
Details
Power supplies should be of the same input type and power
rating.
Action
Install matched power supplies and review this manual for
proper configuration.
PSU1201
Message
Power supply redundancy is lost.
Details
The power supply tries to operate in a degraded state.
System Performance and power redundancy may be
degraded or lost.
Action
Check input power. Reinstall the power supply. If the issue
persists, see
PSU1204
Message
The power supplies are not redundant. Insufficient resources
to maintain normal operations.
Details
The current power operational mode is non-redundant
because of a power supply exception, a power supply
inventory change, or a system power inventory change.