Installation and alignment, Warning, Caution – Banner EZ-SCREEN Safety Light Curtain Systems User Manual
Page 37
page
37
Banner Engineering Corp.
•
Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Installation and Alignment
EZ-SCREEN Grid
Instruction Manual
Dual-Channel
Safety Stop Circuit
Single-Channel
Safety Stop Circuit
NOTE:
See pages 33-34
for explanation
of single- and
dual-channel
stop circuits
* Installation of transient suppressors across the coils of
FSD1 and FSD2 is recommended. NOTE: Do not exceed
OSSD maximum load capacitance specification.
1) See Section 3.5 for
more information on
Reset input and hookup.
2) See Section 3.7.3 for
information on EDM
input and hookup.
+24V dc
0V dc
Reset
PE 1
dc Com 2
+24V dc 3
(Not Used) 4
RESET 5
EDM1 6
EDM2 7
OSSD1 8
OSSD2 9
EZ-SCREEN
Receiver
(1)
(2)
*
*
FSD
1
FSD
2
+
+
Figure 3-16. EZ-SCREEN receiver generic hookup – FSD (2-channel EDM, key reset)
WARNING . . .
Proper Wiring
The generalized wiring
configurations shown are provided
only to illustrate the importance of
proper installation.
The proper wiring of the EZ-
SCREEN Grid System to any
particular machine is solely the
responsibility of the installer and
end user.
!
PE 1
dc Com 2
+24V dc
+24V dc
0V dc
3
TEST2 4
or
TEST1 5
(Not Used) 6
+24V dc 7
dc Com 8
PE 9
EZ-SCREEN
Emitter
Auxiliary power
connections
(see Section 3.5)
Open to test
(1)
1) TEST input must be
jumpered if not used.
Typically a Normally
Open switch held
closed. See Section
3.7.4 for information on
TEST input and hookup.
Figure 3-15. EZ-SCREEN emitter generic hookup
CAUTION. . .
Shock Hazard
Always disconnect all
power from the EZ-SCREEN System
and the guarded machine before
making any connections or
replacing any component. Use
extreme caution to avoid electrical
shock at all times.
Serious bodily injury or death
could result.
WARNING . . .
OSSD Interfacing
To ensure proper
operation, the EZ-SCREEN OSSD
output parameters and machine
input parameters must be
considered when interfacing the EZ-
SCREEN solid-state OSSD outputs
to machine inputs.
Machine Control circuitry must be
designed so that the maximum load
resistance value is not exceeded
and that the maximum specified
OSSD OFF-state voltage does not
result in an ON condition.
Failure to properly interface the
OSSD outputs to the guarded
machine could result in serious
bodily injury or death.
!