Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 76

C-8
VSM500 DeviceNet Option Board
Instance Data Format: Output Assemblies (Continued)
1
If speed references are outside of their min/max limits, the drive ignores them and previous speed
reference will be maintained.
2
0 = 0 Hz, 1200 = 120.0 Hz.
The following table defines the possible settings of the Preset bits in Instance 106.
The following table indicates the I/O Assembly Data Attribute mapping for Output
Assemblies.
Instance 106 Data Format (Preset Control with Speed)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset RunRev
RunFwd
1
Preset 2
Preset 1
Preset 0
2
1
Speed Ref Hz (0.1 Hz) (Low Byte)
2
3
1
Speed Ref Hz (0.1 Hz) (High Byte)
2
Preset 2
Preset 1
Preset 0
Source of Speed Reference
0
0
0
Speed Ref Hz (bytes 2 and 3 of the output assembly)
0
0
1
Parameter 51 [
PRESET
1]
0
1
0
Parameter 52 [
PRESET
2]
0
1
1
Parameter 53 [
PRESET
3]
1
0
0
Parameter 54 [
PRESET
4]
1
0
1
Parameter 55 [[
PRESET
5]
1
1
0
Parameter 56 [
PRESET
6]
1
1
1
Parameter 57 [[
PRESET
7]
Data Component
Name
Class
Instance
Number
Attribute
Name
Number
Name
Number
RunFwd
Supervisor
0x29
1
Run 1
3
RunRev
Supervisor
0x29
1
Run 2
4
Fault Reset
Supervisor
0x29
1
Fault Reset
12
NetCtrl
Supervisor
0x29
1
NetCtrl
5
DN Preset Cmd
Supervisor
0x29
1
DNet Preset Command
102
NetRef
AC Drive
0x2A
1
Net Ref
4
Speed Ref RPM
Supervisor
0x29
1
DNet Speed Ref RPM
103
Speed Ref Hz
Supervisor
0x29
1
DNet Speed Ref Hz
104