Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 54

7-4
VSM500 DeviceNet Option Board
9
0x6312
F.Id
EEPROM Drive
ID
Contents of the EEPROM
is corrupted.
- Reset parameters to default values and
cycle power.
- If fault persists, replace VSM500 unit.
10
0x7700
F.dcn
Keypad
Disconnect
Keypad cable
disconnected while
VSM500 unit under
power.
Remove power from the VSM500 unit.
Check keypad cable connection. Reapply
power to the VSM500 unit.
11
0x7701
F.ddP
Keypad Fixed
Pattern
Keypad cable connected
while VSM500 unit under
power.
Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.
12
0x7702
F.dSF
Keypad
Redundant Start
Keypad hardware failure.
Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.
13
0x5301
F.rSF
TB Redundant
Start
Regulator board failure.
Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.
14
0x7703
F.drc
Keypad Connect Keypad cable connected
while VSM500 unit under
power.
Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.
15
0x3221
F.LU
Under Voltage
while Running
Low input line or
temporary loss of input
line.
Check input line to verify voltage is within
operating specifications.
20
0x6311
F.dnE
DNet EEPROM
Fault
DeviceNet option board
EEPROM has invalid
data.
Use parameter 113 [
RESET
] to reset option
board parameters to factory defaults.
21
0x7502
F.dnU
DNet
Unrecoverable
Fault
No communication is
occurring. Fault occurs
when duplicate node
address exists or wrong
data rate is set.
Check DIP switch settings on the
DeviceNet option board for proper data
rate and node address. If DIP switches 7
and 8 on the DeviceNet option board are
both set to On, check parameter 103 [
NV
MAC
ID
] and parameter 104 [
NV
BAUD
RATE
]. Then reset the option board.
22
0x7500
F.dnP
No DNet Power 24 volt network power is
not detected.
Check DeviceNet connector at
Communication Module. Also, check
network’s power supply.
23
0x7501
F.dnL
DNet Lost I/O
Connection
Polled I/O connection
timed out.
Check DeviceNet master device for correct
operation (i.e., powered up, scanner online,
etc.).
24
0x7504
F.dnF
DNet Forced
Fault
Control Supervisor Object
(Class Code 0x29)
attribute 17 was set to 1.
Clear fault.
25
0x7505
F.dnC
DNet Comm
Fault
Communication failure
between DeviceNet
option board and unit.
Check the unit cable connecting the
DeviceNet option board and VSM500 unit.
1
Parameter fault codes are viewed in parameter 10 [
LAST
FAULT
]. DeviceNet fault codes are read from Class 0x29, Instance 1, Attribute 13.
Display fault codes are viewed on the LED display on the local operator control keypad.
Fault Codes
1
Name
Description
Corrective Action
Parameter
Value
DeviceNet Display