5 commissioning the vsm500 unit for devicenet – Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 17
Installing the DeviceNet Option Board
2-3
Step 6. Before reconnecting the cover (shown in figure 2.5), commission the
VSM500 unit and connect it to the network (instructions in sections 2.5 and
2.6).
2.5
Commissioning the VSM500 Unit for DeviceNet
Step 1. Verify that power has been removed from the VSM500 unit and network.
Step 2. On the VSM500 Integrated drive/motor, set the drive setup DIP switch in
position 10. The setting takes effect when the VSM500 unit first receives
power. Cycle power after changing this setting.
Important: The drive requires a stop input at the control terminal bock, regardless of
the setting of parameter 34 [
START
SOURCE
].
!
ATTENTION: Pen ink or pencil lead may damage the switches on the
DeviceNet option board. Do not use a pen or pencil to set the switches.
Failure to observe these precaution could result in damage to equipment.
Table 2.1 – Drive Setup Switch 10 Settings
Setting
Description
0 (OFF)
VSM500 unit uses settings of DIP switches and rotary switches. You can
use DeviceNet only for monitoring the VSM500 unit.
1 (ON)
VSM500 unit uses settings of parameters in EEPROM. You can use
DeviceNet to program, control, and monitor the VSM500 unit.
Figure 2.3 – Switches on the VSM500 Drive Unit and DeviceNet Option Board
DC+
DC-
DBR
T/L3
S/L2
R/L1
PE
ON
1
2
34
5
6
78
9
10
ON
1
2
3456
78
On= 1
Off = 0