3 fault codes – Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 53

Troubleshooting
7-3
7.3
Fault Codes
When there is a fault, you can view the fault code using the value in parameter 10
[
LAST
FAULT
], the value of Class 0x29 (Control Supervisor Object), Instance 1,
Attribute 13 (Fault Code), or the display on the keypad.
Fault Codes
1
Name
Description
Corrective Action
Parameter
Value
DeviceNet Display
0
0x0000
No Fault
Normal operation.
No action required.
1
0x5300
F.FL
Function Loss
Open connection on
Function Loss control
terminal block inputs
(terminals 7 and 11).
- Check and restore the Function Loss
connection on the terminal block. Refer to
VSM500 Integrated Drive/Motor User
Manual.
- Check the external sensors wired into the
Function Loss string.
2
0x2220
F.OC
Over Current
Shaft rotation blocked.
Excessive driven load.
Input power is not
correctly wired to the
VSM500 unit.
Motor section ground
fault.
- Check for obstructions to shaft rotation.
- Reduce excessive load.
- Increase accel/decel time using the rotary
switches or parameter 32 [
ACCEL
TIME
]
and parameter 33 - [
DECEL
TIM
e].
- Verify that input wiring is correctly
connected. Refer to the VSM500
Integrated Drive/Motor User Manual.
- Check motor section for ground fault.
Replace VSM500 unit if a ground fault is
detected.
3
0x7122
F.OL
Motor Overload Excessive current to
motor for an extended
time due to excessive
load or short circuit.
- Check for obstruction to shaft rotation.
- Reduce the driven load.
- Check input wiring is correctly connected.
Refer to the VSM500 Integrated
Drive/Motor User Manual.
- Check for blower obstruction.
- Replace blower if required.
4
0x3210
F.HU
Over Voltage
High input line.
Deceleration time is too
fast or overhauling load.
- Check input line to verify that voltage is
within operating specification.
- Increase deceleration time using the
accel/decel rotary switch. Refer to the
VSM500 Integrated Drive/Motor User
Manual.
5
0x3220
F.LU
Under Voltage
while Stopped
Low input line or
temporary loss of input
line.
Check input line to verify voltage is within
operating specifications.
6
0x4310
F.OH
Over
Temperature
Operating environment is
too hot.
Blower is blocked or not
operating.
Excessive driven load.
- Check the application site and verify the
ambient temperature is within the
operating specification.
- Check for blower obstruction. Replace
blower if required.
- Reduce load or make sure VSM500 unit
matches the application requirement.
7
0x7510
F.CL
Communication
Loss
Communication between
the DeviceNet option
board and the drive has
failed.
Check cable connection between the
regulator board and DeviceNet option
board.
8
0x6310
F.dCH
Parameter
Checksum
Contents of the EEPROM
is corrupted.
Reset parameters to default values and
cycle power.
1
Parameter fault codes are viewed in parameter 10 [
LAST
FAULT
]. DeviceNet fault codes are read from Class 0x29, Instance 1, Attribute
13. Display fault codes are viewed on the LED display on the local operator control keypad.