Page 18

2-4
VSM500 DeviceNet Option Board
Step 3. On the DeviceNet option board, set switches 6 through 1 to a unique
DeviceNet address between 0 and 63. The default switch setting is 63.
Step 4. On the DeviceNet option board, set switches 7 and 8 to select the data rate
at which the network is operating. The default switch setting is to use the
setting of parameter 104 [
NV
BAUD
RATE
].
Table 2.2 – DeviceNet Option Board Switch Settings (Switches 1-6)
Node
Address
1
Switch
6 ----> 1
Node
Address
1
Switch
6 ----> 1
Node
Address
1
Switch
6 ----> 1
Node
Address
1
Switch
6 ----> 1
0
000000
16
010000
32
100000
48
110000
1
000001
17
010001
33
100001
49
110001
2
000010
18
010010
34
100010
50
110010
3
000011
19
010011
35
100011
51
110011
4
000100
20
010100
36
100100
52
110100
5
000101
21
010101
37
100101
53
110101
6
000110
22
010110
38
100110
54
110110
7
000111
23
010111
39
100111
55
110111
8
001000
24
011000
40
101000
56
111000
9
001001
25
011001
41
101001
57
111001
10
001010
26
011010
42
101010
58
111010
11
001011
27
011011
43
101011
59
111011
12
001100
28
011100
44
101100
60
111100
13
001101
29
011101
45
101101
61
111101
14
001110
30
011110
46
101110
62
111110
15
001111
31
011111
47
101111
63
111111
1
If switches 7 and 8 are both On (1), then the DeviceNet option board uses the node address from parameter 103 [
NV
MAC
ID
]. The default
parameter setting is 63.
Table 2.3 – DeviceNet Option Board Switch Settings (Switches 7-8)
Data Rate
Switch 8
Switch 7
125 kBPS
0
0
250 kBPS
0
1
500 kBPS
1
0
Set by parameter 104 [
NV
BAUD
RATE
]
1
1
The default parameter setting is autobaud.
1