Chapter 2 System Validation

Configure Your Controller Serial Port

The Micro800 controller communicates with PanelView Component terminal and Kinetix 3 drive through the embedded
serial port and 2080-SERIALISOL plug-in. The embedded serial port is called channel 2 and the first plug-in slot is called
channel 5.

The following settings are used for each port.

Table 3 -

Embedded Serial Port

Table 4 - 2080-SERIALISOL Plug-in Module

Parameter

Setting

Driver

CIP Serial

Baud Rate

38400

Parity

None

Station Address

1

Advanced Settings

Error Detection

CRC

Embedded Responses

After One Received

Duplicate Packet Detection

TRUE

ACK Timeout (x20ms)

50

NAK Retries

3

ENQ Retries

3

Transmit Retries

3

RTS off-Delay

0

RTS Send-Delay

0

Parameter

Setting

Driver

Modbus RTU

Baud Rate

19200

Parity

None

Modbus role

Modbus RTU Master

Advanced Settings

Media

RS485

Data bits

8

Stop bits

1

Response Timer

200

Broadcast Pause

200

Inter-Char Timeout

0

RST Pre-Delay

0

RTS Post-Delay

0