Rockwell Automation 1794-Lxxxx PhaseManager User Manual
Page 95

Publication LOGIX-UM001B-EN-P - April 2010
95
Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)
Appendix A
Execution:
Condition
Relay Ladder Action
Structured Text Action
Prescan
The rung-condition-out is set to false.
No action taken.
Rung-condition-in is false
The rung-condition-out is set to false.
N/A
Rung-condition-in is true
The instruction executes.
N/A
Scan of structured text
N/A
In structured text, instructions execute each time
they are scanned. To limit the scan of an instruction,
use a qualifier of an SFC action and/or a structured
text construct.
Instruction execution
Substate
Action
Substate
Action
pausing
• The substate = paused.
• The Paused bit of the PHASE tag
= 1.
• The rung-condition-out = false.
pausing
• The substate = paused.
• The Paused bit of the PHASE tag
= 1.
not pausing
The rung-condition-out = true.
not pausing
No action taken.
Postscan
The rung-condition-out is set to false.