Rockwell Automation 1794-Lxxxx PhaseManager User Manual
Page 83

Publication LOGIX-UM001B-EN-P - April 2010
83
Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)
Appendix A
download recipe control verses
manual phase control
Download Batch Data
DINT[0]
4
DINT[1]
parameter ID in which to store the value
In the result value:
0 = recipe control
1 = manual phase control
download current mode of the
phase
Download Batch Data
DINT[0]
5
DINT[1]
parameter ID in which to store the value
In the result value:
0 = P - Auto mode
1 = O - Auto mode
download the low limit of an input
parameter
Download Batch Data
DINT[0]
6
The input parameter tag stores the low
limit.
download the high limit of an input
parameter
Download Batch Data
DINT[0]
7
The input parameter tag stores the high
limit.
download data about the container
currently in use.
Download Material Track Data
Container In Use
DINT[0]
1
DINT[1]
attribute ID
DINT[2]
parameter ID in which to store the value
download data about the current
material inside the container
currently in use.
Download Material Track Data
Container In Use
DINT[0]
2
DINT[1]
attribute ID
DINT[2]
parameter ID in which to store the value
download data about the current
lot inside the container currently in
use.
Download Material Track Data
Container In Use
DINT[0]
3
DINT[1]
attribute ID
DINT[2]
parameter ID in which to store the value
upload data about the container
currently in use
Upload Material Track Data
Container In Use
DINT[0]
1
DINT[1]
attribute ID
DINT[2]
parameter ID that has the value
upload data about the current
material inside the container
currently in use.
Upload Material Track Data
Container In Use
DINT[0]
2
DINT[1]
attribute ID
DINT[2]
parameter ID that has the value
upload data about the current lot
inside the container currently in
use.
Upload Material Track Data
Container In Use
DINT[0]
3
DINT[1]
attribute ID
DINT[2]
parameter ID that has the value
download the current binding's
container priority
Download Container Binding
Priority
DINT[0]
parameter ID in which to store the value
upload a new container priority for
the current binding
Upload Container Binding Priority
DINT[0]
parameter ID that has the value
If You Want To
Then Configure The PXRQ Instruction As Follows
External Request
Data Value
Array Element
Value