Equipment phase new parameters (prnp) – Rockwell Automation 1794-Lxxxx PhaseManager User Manual
Page 89

Publication LOGIX-UM001B-EN-P - April 2010
89
Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)
Appendix A
Equipment Phase New
Parameters (PRNP)
Use the PRNP instruction to clear the NewInputParameters bit of an
equipment phase.
Operands:
Relay Ladder
none
Structured Text
none
You must enter the parentheses ( ) after the instruction mnemonic, even
though there are no operands.
Description:
The PRNP instruction clears the NewInputParameters bit of the equipment
phase.
Arithmetic Status Flags:
not affected
Fault Conditions:
none
When FactoryTalk Batch software has new
parameters for an equipment phase, it sets the
NewInputParameters bit for the phase.
After you download the parameters, use the
PRNP instruction to clear the bit.