Rockwell Automation MD65 EtherNet/IP Communication Module User Manual
Page 92
9-4
EtherNet/IP Communications Module
9.1.3 NET A Status Indicator
Table 9.3 – NET A Status Indicator: State Definitions
Status
Cause
Corrective Action
Off
The module and/or
network is not
powered, the
module is not
connected properly
to the network, or
the module needs
an IP address.
•
Securely connect the module to
the drive using the Internal
Interface (ribbon) cable and to
the network using an Ethernet
cable.
•
Correctly connect the Ethernet
cable to the Ethernet connector.
•
Set a unique IP address using a
BOOTP server or disabling
BOOTP and using parameters.
•
Apply power to the drive and
network.
Solid Red
The device has
detected an error
and is incapable of
communicating on
the network.
•
Replace the module.
Flashing
Red
An EtherNet/IP
connection has
timed out.
•
Place the scanner in RUN
mode.
•
Check the amount of traffic on
the network.
Flashing
Red/
Green
The module is
performing a self
test.
•
No action is required.
Flashing
Green
The module is
properly connected
but is not
communicating
with any devices
on the network.
•
Place the controller in RUN
mode.
•
Program a controller or peer
device to recognize and
transmit I/O or make a
messaging connection to the
module.
•
Configure the module for the
program in the controller.
Solid
Green
The module is
properly connected
and
communicating
with the network.
•
No action required.