EtherNet/IP Communications Module
8.6.1 Main Routine
The Main Routine reads the network Input Image from the scanner,
calls the various drive control subroutines, and writes the network
Output Image to the scanner. See figure 8.6.
Figure 8.6 – Main Routine
ControlLogix to
The ControlLogix system consists of a 1756-ENBT in slot 5 communicating over Ethernet with a MD65 drive/ MDCOMM-
ENET EtherNet/IP module.
The I/O image is as follows:
INPUT (4 INT words) OUTPUT (2 INT words)
MD65-Demo:I.Data[0] = ENBT Overhead MD65-Demo:I.Data[0] = MD65 Logic Command
MD65-Demo:I.Data[1] = ENBT Overhead MD65-Demo:I.Data[1] = MD65 Reference
MD65-Demo:I.Data[2] = MD65 Logic Status
MD65-Demo:I.Data[3] = MD65 Feedback
Logic Status information rungs are provided for display purposes only. The MD65_Demo: I.Data[2].x.bits could be used
directly elsewhere in the ladder program.
0
MD65 Demo
Logic Status
READY
MD65_Demo:I.Data[2].0
MD65
READY
Drive_Ready
ControlLogix to MD65 on EtherNet/IP Demo
The ControlLogix system consists of a 1756-ENBT in slot 5 communicating over Ethernet with
The I/O image is as follows:
INPUT (4 INT words) OUTPUT (2 INT words)
Logic Status information rungs are provided for display purposes only. T
directly elsewhere in the ladder program.
1
MD65 Demo
Logic Status
ACTIVE
MD65_Demo:I.Data[2].1
MD65
ACTIVE
Drive_Active
2
MD65 Demo
Logic Status
ACTUAL
DIRECTION
MD65_Demo:I.Data[2].2
MD65
FORWARD
Drive_Forward
3
/
MD65 Demo
Logic Status
ACTUAL
DIRECTION
MD65_Demo:I.Data[2].2
MD65
REVERSE
Drive_Reverse
4
MD65 Demo
Logic Status
FAULT
MD65_Demo:I.Data[2].7
MD65
FAULT
Drive_Fault
5
MD65 Demo
Logic Status
AT SPEED
MD65_Demo:I.Data[2].8
MD65
AT SPEED
Drive_At_Speed