1 to enable the module web pages – Rockwell Automation MD65 EtherNet/IP Communication Module User Manual
Page 35
![background image](/manuals/581228/35/background.png)
Configuring the EtherNet/IP Module
4-13
4.9.1 To Enable the Module Web Pages
Set the Web Pages Switch (SW2) to the “Enable Web” (up)
position. Refer to figure 3.1 and table 3.2
Important:For a change to the switch setting to take effect, the
module must be reset.
Bit 0 of parameter 30 (Web Features) is used to protect the
configured settings for e-mail notification. By default, settings are
not protected. To protect an e-mail configuration, set the value of E-
mail Cfg Bit 0 to “0” (Disabled). You can unprotect the configuration
by changing Bit 0 back to “1” (Enabled). E-mail notification will
always remain active regardless of whether or not its settings are
protected - unless e-mail notification was never configured. For
more information about configuring module e-mail notification or
stopping e-mail messages, refer to chapter 10.
Bit 0 is the right-most bit. In figure 4.12, it is highlighted and equals
“1”.
Changes to this parameter take effect immediately. A reset is not
required.
Bit 1 of parameter 30 (Web Features) protects the configuration of
parameters (names and values) shown in the “process status” fields
on both the Home page (Single Mode only) and Process Display
pop-up window. By default, this configuration is not protected. To
protect the configuration, set the value of Proc Dsp Cfg Bit 1 to “0”
(Disabled). You can unprotect the configuration by changing Bit 1
back to “1” (Enabled). For more information about configuring the
parameters for display, refer to chapter 10.
Figure 4.12 – I/O Configuration Screen on an LCD OIM
Access Control
MDCOMM-ENET
Parameter #: 30
x x x x x x 1
1
Value
Description
0
E-mail Cfg (Default = 1= Enabled)
1
Proc Dsp Cfg (Default = 1= Enabled)
2 - 7
Not Used